BEEexams.in

Free, open exam prep for BEE Energy Managers & Auditors · Paper-1 & Paper-3

BEE Exam Prep › Paper-3 › Formula & concept guide

Paper-3 — Formula & Concept Guide

Energy Efficiency in Electrical Utilities — all 10 chapters, all 137 formulas (the same list as the Formula & Unit Workbook, so nothing is missing).
For every formula: what each symbol means and its unit, what the formula tells you, a worked example from a real exam question, and the exam trap. Plus 26 photographs of the actual equipment, 16 diagrams, 20 constants, 48 definitions and 23 verified online videos. Values are the 2014 BEE Book-3's.
▶ Download the whole guide as one PDF · Numericals drill
Ch 1 · Electrical Systems (19 formulas)Ch 2 · Electric Motors (14 formulas)Ch 3 · Compressed Air System (14 formulas)Ch 4 · HVAC and Refrigeration System (13 formulas)Ch 5 · Fans and Blowers (14 formulas)Ch 6 · Pumps and Pumping System (12 formulas)Ch 7 · Cooling Tower (12 formulas)Ch 8 · Lighting System (13 formulas)Ch 9 · DG Set System (13 formulas)Ch 10 · Buildings and ECBC (13 formulas)
Constants to memorise (used all through the paper)
1 TR (Ton of Refrigeration) in kcal/hr
3024 kcal/hr
1 TR in kW
3.51 kW
1 TR in BTU/hr
12,000 BTU/hr
1 kW in kcal/hr
860 kcal/hr
1 kWh in kcal
860 kcal
1 BHP in kW
0.746 kW
Acceleration due to gravity, g
9.81 m/s²
Density and specific heat of water
1000 kg/m³ ; Cp = 1 kcal/kg °C
1 kg/cm² pressure as water head
10 m of water column
1 m³/min in cfm
35.31 cfm
Density of air at 0 °C (fans)
1.293 kg/m³
Molecular weight of air
28.92 kg/kg-mole
Maximum luminous efficacy
683 lm/W at 555 nm
Condenser water flow per TR
0.91 m³/hr per TR (4 gpm/TR)
Evaporation per 10,00,000 kcal heat rejected (cooling tower)
1.8 m³
DG exhaust gas: mass per kWh and Cp
8 kg/kWh ; 0.25 kcal/kg °C
Stray load loss of a motor (IS/IEC)
0.5 % of input power
Why 102 in fan efficiency formula
1000 ÷ 9.81 (converts m³/s × mmWC into kW)
Temperature in Kelvin
K = °C + 273
ECBC applies to buildings with
connected load ≥ 100 kW or contract demand ≥ 120 kVA

Chapter 1 · Electrical Systems

~23 marks (15 %) — the top chapter with HVAC. PF/kVAr, transformer losses at part load, maximum demand and AT&C losses come every year as numericals.

Distribution transformer — iron loss is constant, copper loss rises with load²
Distribution transformer — iron loss is constant, copper loss rises with load²Photo: Cjp24 · CC BY-SA 4.0 · source
Power-factor correction panel: capacitor banks switched in steps by an automatic PF controller
Power-factor correction panel: capacitor banks switched in steps by an automatic PF controllerPhoto: Beuhri at Dutch Wikipedia · Public domain · source
Three-phase energy meter — records kWh, and kVA maximum demand over 30-minute windows
Three-phase energy meter — records kWh, and kVA maximum demand over 30-minute windowsPhoto: Gpkp · CC BY-SA 4.0 · source

Power factor

PF = cos φ = kW ÷ kVA
Symbols · units
SymbolskW = real power, kVA = apparent power
Answer unitno unit (0 to 1)
Book topicPower factor
HV incoreLV out to loadload kWheat: iron + copper losscapacitorkW

Where each value sits: kW → kVA, kVAr, kW · kVA → kVA, kVAr, kW

▶ Try it: Power factor: add capacitor kVAr — watch the triangle shrink
kW (unchanged)
What it means

The fraction of the current that does real work. PF = 1 means every ampere is useful; PF 0.7 means the cables and transformer carry 43 % more current than the work needs.

Worked example. kW 812, kVA 1,160 → PF = 0.70.
Exam trap. PF is a ratio, never a percentage of energy saved.

Apparent power, 3-phase

kVA = √3 × V × I ÷ 1000
Symbols · units
SymbolsV = line voltage (V), I = line current (A)
Answer unitkVA
Book topicPower triangle
HV incoreLV out to loadload kWheat: iron + copper losscapacitorVI

Where each value sits: V → receiving-end Er, V · I → copper / load loss ∝ load²

What it means

What the supply actually has to deliver — the voltage times the current, before asking how much of it does work. Cables, switchgear and transformers are rated in kVA for this reason.

Worked example. 415 V, 100 A → √3 × 415 × 100 ÷ 1000 = 71.9 kVA.
Exam trap. Use the line-to-line voltage (415 V), not 230 V, for 3-phase.

Real power, 3-phase

kW = √3 × V × I × PF ÷ 1000
Symbols · units
SymbolsV (V), I (A), PF (no unit)
Answer unitkW
Book topicPower triangle
HV incoreLV out to loadload kWheat: iron + copper losscapacitorVIPF

Where each value sits: V → receiving-end Er, V · I → copper / load loss ∝ load² · PF → kVAr, φ₁, φ₂, PF

What it means

The power that turns into heat, motion or light — what the kWh meter records. It is the apparent power times the power factor.

Worked example. 415 V, 100 A, PF 0.8 → 57.5 kW.
Exam trap. If PF is not given, do not assume 1 — the question usually gives it.

Relation between kW, kVAr and kVA

kVA² = kW² + kVAr²
Symbols · units
SymbolskW, kVAr, kVA
Answer unitkVA
Book topicPower triangle
HV incoreLV out to loadload kWheat: iron + copper losscapacitorkW

Where each value sits: kW → kVA, kVAr, kW · kVAr → kVA, kVAr, kW · kVA → kVA, kVAr, kW

▶ Try it: Power factor: add capacitor kVAr — watch the triangle shrink
kW (unchanged)
What it means

Pythagoras on the power triangle: kW along the base, kVAr up the side, kVA on the diagonal. Given any two you can find the third.

Worked example. kW 812, kVAr 828 → kVA = √(812² + 828²) = 1,160.
Exam trap. kVA is NOT kW + kVAr — they add as a triangle, not in a straight line.

Capacitor rating to improve power factor

kVAr = kW × (tan φ₁ − tan φ₂)
Symbols · units
SymbolskW = average operating load; φ₁ = cos⁻¹(existing PF); φ₂ = cos⁻¹(improved PF)
Answer unitkVAr
Book topicPF correction
HV incoreLV out to loadload kWheat: iron + copper losscapacitorkWφ₁

Where each value sits: kW → % load, kVA, kW · φ₁ → kVAr, φ₁, φ₂, PF · φ₂ → kVAr, φ₁, φ₂, PF

▶ Try it: Power factor: add capacitor kVAr — watch the triangle shrink
kW (unchanged)
What it means

How many kVAr of capacitors to add so the existing kW load reaches the target PF. Convert each PF to its angle (φ = cos⁻¹ PF), take the tangents, multiply the difference by the kW.

Worked example. 627 kW from PF 0.72 (tan 0.964) to 0.95 (tan 0.329): 627 × 0.635 = 398 kVAr (the book's example). Useful tangents: 0.7→1.02, 0.8→0.75, 0.85→0.62, 0.9→0.48, 0.95→0.33, 1→0.
Exam trap. Multiply the OPERATING kW (average load), not the kVA and not the nameplate. A capacitor's kVAr output falls with the square of the voltage: at 400 V a 415 V unit gives (400/415)² = 93 %.

Line (copper) loss

P = I² × R
Symbols · units
SymbolsI = current (A), R = resistance (Ω)
Answer unitW
Book topicDistribution losses
HV incoreLV out to loadload kWheat: iron + copper losscapacitorI

Where each value sits: I → copper / load loss ∝ load² · R → copper / load loss ∝ load²

What it means

Heat wasted in a conductor. Because it depends on the SQUARE of the current, halving the current (by raising voltage or improving PF) cuts the loss to a quarter.

Worked example. 100 A through 0.1 Ω → 1,000 W; at 50 A → 250 W.
Exam trap. Loss ∝ I², not ∝ I.

% reduction in distribution loss when tail-end PF is raised

[1 − (PF₁ ÷ PF₂)²] × 100
Symbols · units
SymbolsPF₁ = existing PF, PF₂ = improved PF
Answer unit%
Book topicLocation of capacitors
HV incoreLV out to loadload kWheat: iron + copper losscapacitorPF₁

Where each value sits: PF₁ → kVAr, φ₁, φ₂, PF · PF₂ → kVAr, φ₁, φ₂, PF

What it means

Raising the PF at the load end lowers the current for the same kW, so the I²R loss in the upstream cables falls by 1 − (old PF ÷ new PF)².

Worked example. 0.85 → 0.95: 1 − (0.85/0.95)² = 1 − 0.80 = 19.9 %. 0.8 → 0.95: 29 % (2016/2017 objective).
Exam trap. Ratio old ÷ new, then SQUARE it — then subtract from 1.

Maximum demand registered by MD meter

MD = Σ(kVA × minutes) ÷ demand interval (30 min)
Symbols · units
SymbolskVA of each period; duration in minutes
Answer unitkVA
Book topicMaximum demand
MD meter — 30-minute windowskVA per intervalfundamental 50 Hz + harmonicskVA

Where each value sits: kVA → kVA × minutes / 30-min interval · duration → kVA × minutes / 30-min interval

What it means

The meter averages kVA over each 30-minute window and remembers the highest window of the month. You pay demand charges on that peak even if it happened once.

Worked example. (2,500×4 + 3,600×12 + 4,100×6 + 3,800×8) ÷ 30 = 3,607 kVA.
Exam trap. It is the average over the interval, not the instantaneous peak.

Transformer loss at any load (from % load)

P = P no-load + (% load ÷ 100)² × P full-load load loss
Symbols · units
Symbolsno-load (iron) loss and full-load copper loss in kW or W
Answer unitkW (or W)
Book topicTransformer losses
HV incoreLV out to loadload kWheat: iron + copper losscapacitorno-load

Where each value sits: no-load → iron / no-load loss (constant)

▶ Try it: Transformer: load it up — iron loss stays flat, copper loss grows with load²
% load iron losscopper loss
What it means

Iron (no-load) loss is constant whenever the transformer is energised; copper (load) loss rises with the SQUARE of the load. Efficiency is highest where the two are equal.

Worked example. 750 kVA, 1,200 W no-load, 7,200 W full-load Cu, at 60 %: 1,200 + 0.36 × 7,200 = 3,792 W (2025 Q7).
Exam trap. At 60 % load the copper loss is 0.36 × full-load, never 0.6 ×.

Transformer loss at any load (from kVA)

= No-load loss + (actual kVA ÷ rated kVA)² × Full-load loss
Symbols · units
SymbolskVA; losses in kW or W
Answer unitkW (or W)
Book topicTransformer losses
HV incoreLV out to loadload kWheat: iron + copper losscapacitorkVA

Where each value sits: kVA → kVA, kVAr, kW · losses → kVA, kVAr, kW

▶ Try it: Transformer: load it up — iron loss stays flat, copper loss grows with load²
% load iron losscopper loss
What it means

Same idea using the actual kVA carried: the load fraction is actual ÷ rated kVA.

Worked example. Rated 1,000 kVA carrying 500 kVA → fraction 0.5 → Cu loss = 0.25 × full-load Cu loss.
Exam trap. Load fraction from kVA, not from kW.

Voltage regulation

% Regulation = (Es − Er) ÷ Er × 100
Symbols · units
SymbolsEs = sending-end voltage, Er = receiving-end voltage (V)
Answer unit%
Book topicVoltage regulation
HV incoreLV out to loadload kWheat: iron + copper losscapacitorEsEr

Where each value sits: Es → sending-end Es · Er → receiving-end Er, V

What it means

How much the voltage drops between the sending and receiving end under load, as a percentage of the receiving-end voltage; big drops mean long or overloaded lines.

Worked example. Es 11.5 kV, Er 11.0 → 4.5 %.
Exam trap. Divide by the RECEIVING end voltage (book formula).

Input energy of a distribution area

Ei = Import − Export
Symbols · units
Symbolsenergy in MU (million units)
Answer unitMU
Book topicAT&C losses
generationDISCOM areaconsumers₹technical + commercial lossenergy

Where each value sits: energy → energy needed at end use

What it means

The energy a DISCOM area actually receives to sell: what it imports minus what it exports to neighbouring areas.

Worked example. Import 12 MU, export 2 MU → 10 MU.
Exam trap. Measured in million units (MU = 10⁶ kWh).

Billing efficiency

BE = Eb ÷ Ei × 100
Symbols · units
SymbolsEb = total energy billed (MU), Ei = input energy (MU)
Answer unit%
Book topicAT&C losses
generationDISCOM areaconsumers₹technical + commercial lossEbEi

Where each value sits: Eb → energy billed Eb · Ei → input energy Ei (import − export)

What it means

Share of the input energy that was actually billed to consumers (metered + un-metered). The rest is technical loss plus theft/unbilled use.

Worked example. Billed 7 MU of 10 MU input → 70 % (book Table 1.7).
Exam trap. Include un-metered billed energy (flat-rate agricultural) in the billed figure.

Amount collected without arrears

Ac = AG − Ar
Symbols · units
SymbolsAG = gross amount collected, Ar = arrears collected (Rs)
Answer unitRs
Book topicAT&C losses
generationDISCOM areaconsumers₹technical + commercial lossAG

Where each value sits: AG → amount billed Ab, collected AG, arrears Ar · Ar → amount billed Ab, collected AG, arrears Ar

What it means

Money collected for THIS year's bills only — arrears belong to earlier years and would inflate the collection efficiency.

Worked example. Gross collected 410 lakh, arrears 40 → 370 lakh.
Exam trap. If arrears are not given, assume Ar = AG − Ab (book note).

Collection efficiency

CE = Ac ÷ Ab × 100
Symbols · units
SymbolsAc = amount collected without arrears, Ab = amount billed (Rs)
Answer unit%
Book topicAT&C losses
generationDISCOM areaconsumers₹technical + commercial lossAcAb

Where each value sits: Ac → amount billed Ab, collected AG, arrears Ar · Ab → energy billed Eb

What it means

Share of the amount billed that was actually paid (this year's bills).

Worked example. 370 ÷ 400 = 92.5 % ≈ 93 %.
Exam trap. Money ratio, not energy.

AT&C (Aggregate Technical & Commercial) loss

AT&C = [1 − (BE × CE)] × 100
Symbols · units
SymbolsBE and CE as fractions
Answer unit%
Book topicAT&C losses
generationDISCOM areaconsumers₹technical + commercial lossBE

Where each value sits: BE → billing efficiency BE

What it means

The DISCOM's total loss: energy lost technically AND commercially (not billed, not collected) as one number — 1 minus the product of the two efficiencies.

Worked example. BE 0.70 × CE 0.93 = 0.651 → AT&C = 34.9 % ≈ 35 % (book). 2025 S-2 asks exactly this chain.
Exam trap. Multiply the two efficiencies as FRACTIONS, then subtract from 1; do not add the two losses.

Total harmonic distortion of current

THD = √(I₃² + I₅² + I₇² + …) ÷ I₁ × 100
Symbols · units
SymbolsI₁ = fundamental current (A); I₃, I₅… = harmonic currents (A)
Answer unit%
Book topicHarmonics
MD meter — 30-minute windowskVA per intervalfundamental 50 Hz + harmonicsI₁I₃

Where each value sits: I₁ → I₁ fundamental · I₃ → I₃, I₅, I₇ harmonics · I₅… → I₃, I₅, I₇ harmonics

What it means

How much the current waveform is polluted by frequencies at multiples of 50 Hz (from VFDs, UPS, rectifiers, CFLs). Root-sum-square of the harmonic currents divided by the fundamental.

Worked example. I₁ 250 A, I₃ 50, I₅ 35 → √(2,500 + 1,225) ÷ 250 = 24.4 % (book example).
Exam trap. Square, add, then root — never a plain sum of the harmonic percentages. Resistive loads (heaters) create no harmonics.

Overall efficiency of an energy chain

η overall = η₁ × η₂ × η₃ × …
Symbols · units
Symbolseach efficiency as a fraction
Answer unit% (or fraction)
Book topic1 unit saved = 2 units generated
generationDISCOM areaconsumers₹technical + commercial losseach

Where each value sits: each → η₁ × η₂ × η₃

What it means

Efficiencies in series multiply. From power station to the motor shaft the book's chain is 0.83 (generation & T&D) × 0.95 × 0.9 × 0.7 ≈ 0.50.

Worked example. Four stages at 83 %, 95 %, 90 %, 70 % → 50 %.
Exam trap. Multiply, do not average.

Energy to be generated for a given end use

= Energy needed at end use ÷ η overall
Symbols · units
SymbolskWh; η as fraction
Answer unitkWh
Book topic1 unit saved = 2 units generated
generationDISCOM areaconsumers₹technical + commercial losskWh

Where each value sits: kWh → energy needed at end use · η: η as fraction

What it means

Because the chain is only ~50 % efficient, every unit saved at the end use saves about two units at the power station — 'one unit saved = two units generated'.

Worked example. 1 kWh saved at the shaft ÷ 0.5 = 2 kWh of generation avoided.
Exam trap. Divide by the efficiency, never multiply.

Power triangle — what a capacitor does

kW — real power (unchanged) kVArkVA (before) kVA after capacitor kVAr = kW (tan φ₁ − tan φ₂)capacitor supplies themagnetising kVAr locally →kVA and current fall,PF = kW ÷ kVA rises

Transformer losses vs load

% loadloss (W) iron (no-load) loss — constant copper loss ∝ (load)² 50 %: Cu = ¼ of full-load Total = iron + (load/100)² × full-load Cu. Max efficiency where iron = copper loss.
Definitions the exam asks
Maximum demand and load factor
MD is the highest 30-minute average kVA in the month; load factor = average load ÷ maximum demand. Improving load factor (shifting loads off-peak) cuts demand charges.
TOD tariff
Time-of-day tariff charges more in peak hours and less off-peak, to encourage shifting load.
Harmonics
Currents at multiples of 50 Hz from non-linear loads (VFDs, UPS, rectifiers, CFLs); they heat transformers, trip breakers and distort voltage. Resistive heaters and incandescent lamps create none.
Automatic PF controller
Switches capacitor steps in and out to hold the target PF as load changes; capacitors at the load end also cut cable losses.
DSM
Demand-side management: the utility shapes customer load — peak clipping, valley filling, load shifting, strategic conservation.
Verified videos for this chapter (YouTube)
Power Factor & Capacitor Sizing — How to Calculate Capacitor kVAR to Improve Power Factor | Step-by-Step Guide · Ahmed Hassanin AcademyTransformer Core/Copper Losses — How to Calculate Transformer Efficiency | Core Losses Explained · Kognito Key

Chapter 2 · Electric Motors

~10 marks: many easy objectives (losses, speed, slip, IE classes) plus the loading and replacement-saving numericals.

Squirrel-cage induction motors with the rotor and cooling fan removed
Squirrel-cage induction motors with the rotor and cooling fan removedPhoto: Zureks · CC BY-SA 3.0 · source
Variable-frequency drive — changes motor speed by changing supply frequency (Ns = 120f/P)
Variable-frequency drive — changes motor speed by changing supply frequency (Ns = 120f/P)Photo: Suyash.dwivedi · CC BY-SA 4.0 · source

Synchronous speed

Ns = 120 × f ÷ P
Symbols · units
Symbolsf = supply frequency (Hz), P = number of poles
Answer unitrpm
Book topicMotor speed
supplystatorrotorloadheat = lossesf

Where each value sits: f → synchronous speed Ns, poles P · P → synchronous speed Ns, poles P

What it means

The speed of the rotating magnetic field; the rotor can never quite reach it. Indian 50 Hz speeds: 3,000 / 1,500 / 1,000 / 750 / 600 / 500 rpm for 2 / 4 / 6 / 8 / 10 / 12 poles.

Worked example. 4 poles: 120 × 50 ÷ 4 = 1,500 rpm.
Exam trap. More poles = slower; poles are always an even number.

Slip

Slip % = (Ns − N) ÷ Ns × 100
Symbols · units
SymbolsNs = synchronous speed, N = actual full-load speed (rpm)
Answer unit%
Book topicMotor speed
supplystatorrotorloadheat = lossesNsN

Where each value sits: Ns → synchronous speed Ns, poles P · N → rotor speed N, slip

What it means

How far the rotor lags the field, as a percentage. Full-load slip of a good motor is 2–5 %; slip rises with load and with poor rotor design (rewinding damage).

Worked example. Ns 1,500, N 1,470 → 2 %.
Exam trap. Slip is measured at the rated (full-load) speed on the nameplate.

Motor power factor

PF = cos φ = kW ÷ kVA
Symbols · units
SymbolskW, kVA
Answer unitno unit
Book topicPower factor
supplystatorrotorloadheat = losseskWkVA

Where each value sits: kW → input kW · kVA → V, I, cos φ, f

What it means

As load falls the working current drops but the magnetising current does not, so PF collapses at light load — lightly loaded motors are the main cause of poor plant PF.

Worked example. Full load PF 0.85; at 25 % load perhaps 0.5.
Exam trap. Low PF at light load is normal, not a fault.

Motor efficiency

η = P out ÷ P in = 1 − (P loss ÷ P in)
Symbols · units
SymbolsP out = output, P in = input, P loss = losses (kW)
Answer unit% (or fraction)
Book topicMotor efficiency
supplystatorrotorloadheat = lossesP out

Where each value sits: P out → synchronous speed Ns, poles P · P in → synchronous speed Ns, poles P · P loss → synchronous speed Ns, poles P

What it means

Output at the shaft divided by electrical input; the difference is heat (I²R in stator and rotor, core, friction & windage, stray). Efficiency is flat from 50–100 % load and falls steeply below 40 %.

Worked example. Input 61.5 kW, output 55 kW → 89.4 % (2023 S-4).
Exam trap. Efficiency is output ÷ input, never input ÷ output.

Input power of a 3-phase motor

P = √3 × kV × I × cos φ
Symbols · units
SymbolskV = line voltage (kV), I = current (A)
Answer unitkW
Book topicMotor loading
supplystatorrotorloadheat = losseskV

Where each value sits: kV → V, I, cos φ, f · I → V, I, cos φ, f

▶ Try it: Motor: measured volts, amps and PF → loading %
What it means

The electrical power the motor is drawing right now, from measured volts, amps and PF.

Worked example. 410 V, 75 A, PF 0.8 → 1.732 × 0.410 × 75 × 0.8 = 42.6 kW (2023).
Exam trap. Voltage in kV in this form of the formula.

Friction & windage + core loss (no-load test)

= No-load input power − (No-load current)² × Stator resistance
Symbols · units
SymbolsW, A, Ω
Answer unitW
Book topicField tests
supplystatorrotorloadheat = lossesno-load kWI no-loadR statorF&W + core

Where each value sits: no-load kW → input kW · I no-load → V, I, cos φ, f · R stator → stator I²R, resistance R · F&W + core → losses, F&W, core, stray

What it means

Run the motor unloaded: nearly all the input is core loss plus bearing/fan (friction & windage) loss, after subtracting the small stator I²R at no-load current.

Worked example. No-load 1,064 W, no-load current 10 A, R 0.5 Ω → 1,064 − 100 × 0.5 = 1,014 W.
Exam trap. Subtract the stator I²R at NO-LOAD current, using the per-phase resistance as the book does.

Stator resistance corrected to operating temperature

R₂ = R₁ × (235 + t₂) ÷ (235 + t₁)
Symbols · units
SymbolsR₁ = resistance at ambient t₁ (°C); t₂ = operating temperature (°C)
Answer unitΩ
Book topicField tests
supplystatorrotorloadheat = lossesR₁t₂

Where each value sits: R₁ → stator I²R, resistance R · t₂ → temperature t₁, t₂

What it means

Copper resistance rises with temperature; the resistance measured cold must be scaled to the running temperature (100–120 °C for modern motors) before calculating I²R loss.

Worked example. R at 30 °C = 0.5 Ω → at 120 °C: 0.5 × (235 + 120)/(235 + 30) = 0.67 Ω.
Exam trap. The constant 235 belongs to copper; it is added to BOTH temperatures.

Rotor I²R (copper) loss

= Slip × (Stator input − Stator I²R loss − Core loss)
Symbols · units
Symbolsslip as a fraction; powers in W
Answer unitW
Book topicField tests
supplystatorrotorloadheat = lossesslippowers

Where each value sits: slip → rotor speed N, slip · powers → synchronous speed Ns, poles P

What it means

Rotor loss is the slip fraction of the power crossing the air gap (stator input minus stator losses).

Worked example. Slip 0.03 × 40,000 W air-gap power = 1,200 W.
Exam trap. Use slip as a fraction (0.03), not 3.

Stray load loss (IS/IEC method)

= 0.5 % of input power
Symbols · units
Symbolsinput power (W)
Answer unitW
Book topicField tests
supplystatorrotorloadheat = lossesinput

Where each value sits: input → V, I, cos φ, f

What it means

Losses that cannot be measured directly (leakage flux, harmonics); the Indian/IEC standard simply assumes 0.5 % of input.

Worked example. Input 50 kW → 250 W.
Exam trap. IEEE 112 measures it (and gives lower efficiency); IS/IEC assumes 0.5 %.

Motor % loading (input method)

= Input kW at existing load ÷ (Nameplate kW ÷ Nameplate η) × 100
Symbols · units
SymbolskW; η as fraction
Answer unit%
Book topicMotor loading
supplystatorrotorloadheat = losseskWη

Where each value sits: kW → input kW · η → output kW, η

▶ Try it: Motor: measured volts, amps and PF → loading %
What it means

Compare measured input with the input the motor would draw at full load (nameplate kW ÷ nameplate efficiency).

Worked example. Input 42.6 kW; rated input 55/0.894 = 61.5 → 69 % (2023 S-4).
Exam trap. Never estimate loading from the current ratio alone — current is not proportional to load at low loads.

Motor % loading (output method)

= Actual operating load ÷ Rated capacity × 100
Symbols · units
SymbolskW
Answer unit%
Book topicMotor loading
supplystatorrotorloadheat = losseskW

Where each value sits: kW → input kW

What it means

Actual mechanical load divided by rated output — used when the shaft load is known (e.g. from pump duty).

Worked example. Pump needs 30 kW from a 37 kW motor → 81 %.
Exam trap. Same units top and bottom (both kW output).

Saving by replacing with an energy-efficient motor

kW saving = kW output × (1 ÷ η old − 1 ÷ η new)
Symbols · units
Symbolsη old, η new as fractions
Answer unitkW
Book topicHigh-efficiency motors
supplystatorrotorloadheat = lossesη

Where each value sits: η → output kW, η · η → output kW, η

What it means

For the same output, a more efficient motor draws less input; the saving is the difference of the two inputs.

Worked example. 22 kW output, η 0.88 → 0.92: 22 × (1/0.88 − 1/0.92) = 1.09 kW; × 6,000 h = 6,540 kWh/yr.
Exam trap. Use the OUTPUT kW in the bracket formula; the reciprocals handle the inputs.

Voltage unbalance (NEMA)

% = Max. deviation from mean of (Vab, Vbc, Vca) ÷ Mean × 100
Symbols · units
Symbolsline voltages (V)
Answer unit%
Book topicVoltage unbalance
supplystatorrotorloadheat = lossesline

Where each value sits: line → V, I, cos φ, f

What it means

Unequal phase voltages; even 1 % unbalance causes 6–10× that in current unbalance and overheats the motor.

Worked example. 410/417/408 V: mean 411.7, max deviation 5.3 → 1.29 % (book).
Exam trap. Deviation from the MEAN divided by the mean, not the spread between max and min.

Additional temperature rise due to voltage unbalance

ΔT = 2 × (% voltage unbalance)²
Symbols · units
Symbols% unbalance
Answer unit°C
Book topicVoltage unbalance
supplystatorrotorloadheat = losses%

Where each value sits: % → Vab, Vbc, Vca

What it means

Each 10 °C hotter halves insulation life; a 2 % unbalance adds 8 °C.

Worked example. 2 % → 2 × 4 = 8 °C.
Exam trap. Square the percentage first, then double.

Motor efficiency and power factor vs load

% of rated load efficiency — flat from 50 to 100 % power factor — keeps falling at light load 40 %below 40 %: both collapse → star mode / downsize
Definitions the exam asks
Motor losses (book split)
Stator + rotor I²R 55–60 %, iron/core 20–25 %, friction & windage 8–12 %, stray 4–5 %.
Energy-efficient motors
IE2/IE3 (IS 12615): lower losses through better steel, more copper, better fans; saving = kW(1/η_old − 1/η_new).
Rewinding
A poorly rewound motor loses 1–2 % efficiency; check no-load current and stator resistance per phase before and after.
Star-delta / star mode
A motor loaded below ~40 % runs better permanently in star (√3 lower voltage): higher efficiency and PF, less magnetising current.
Soft starter
Limits inrush current and mechanical shock at start; it does NOT improve running efficiency.
Verified videos for this chapter (YouTube)
Motor Loss Split & EEM Standards — Tutorial on how to calculate the efficiency of an induction motor · Marayati MarsadekRewinding Effects & Stator Resistance — Simple problems on 3-phase induction motors: Slip, Rotor Frequency(Part-I) · Gargi BasuVoltage Unbalance & Star Mode — Induction Motor--Calcuate Current Given HP, Efficiency and Pf · Raiya Academy

Chapter 3 · Compressed Air System

~20 marks: FAD, leakage, specific power and receiver/pipe sizing numericals; intercooling and dryer theory.

Small reciprocating (piston) air compressor with its receiver
Small reciprocating (piston) air compressor with its receiverPhoto: Sirotmusic · CC BY-SA 4.0 · source
Large two-stage reciprocating compressor — intercooling between stages cuts the work
Large two-stage reciprocating compressor — intercooling between stages cuts the workPhoto: Chris Allen · CC BY-SA 2.0 · source
Air receiver — stores air, smooths demand peaks and separates moisture
Air receiver — stores air, smooths demand peaks and separates moisturePhoto: P1898 · CC BY 4.0 · source
Compressed-air system layout: compressor, after-cooler, receiver, dryer, distribution
Compressed-air system layout: compressor, after-cooler, receiver, dryer, distributionPhoto: Brian S. Elliott · CC BY-SA 4.0 · source

Compressor displacement

= (π ÷ 4) × D² × L × S × X × n
Symbols · units
SymbolsD = bore (m), L = stroke (m), S = speed (rpm), X = 1 single / 2 double acting, n = no. of cylinders
Answer unitm³/min
Book topicVolumetric efficiency
compressorreceiverdryerpipe → usersleakload Tunload tD

Where each value sits: D → bore D, stroke L, speed S, X, n · L → bore D, stroke L, speed S, X, n · S → bore D, stroke L, speed S, X, n · X → bore D, stroke L, speed S, X, n · n → bore D, stroke L, speed S, X, n

What it means

The volume the pistons sweep per minute — the theoretical maximum the machine could deliver.

Worked example. Bore 0.2 m, stroke 0.15 m, 600 rpm, double-acting (X=2), 2 cylinders → 0.785 × 0.04 × 0.15 × 600 × 2 × 2 = 11.3 m³/min.
Exam trap. X = 2 for double-acting cylinders.

Volumetric efficiency

= FAD ÷ Compressor displacement × 100
Symbols · units
Symbolsboth in m³/min
Answer unit%
Book topicVolumetric efficiency
compressorreceiverdryerpipe → usersleakload Tunload tboth

Where each value sits: both → FAD Q, displacement

What it means

How much of the swept volume actually comes out as free air; clearance volume, leakage and valve losses take the rest (typically 65–85 %).

Worked example. FAD 9 m³/min ÷ displacement 11.3 = 80 %.
Exam trap. No power term in this formula — it is volume ÷ volume.

Isothermal power

= P₁ × Q₁ × logₑ r ÷ 36.7
Symbols · units
SymbolsP₁ = absolute intake pressure (kg/cm²), Q₁ = FAD (m³/hr), r = P₂ ÷ P₁
Answer unitkW
Book topicIsothermal efficiency
compressorreceiverdryerpipe → usersleakload Tunload tP₁Q₁r

Where each value sits: P₁ → P₁ intake, P₂ delivery, r = P₂/P₁ · Q₁ → FAD Q, displacement · r → receiver V, P₁ → P₂, time T

What it means

The ideal power if the air were compressed at constant temperature — the lowest possible. Uses the natural log of the pressure ratio.

Worked example. P₁ 1.03 kg/cm² abs, Q₁ 600 m³/hr, r = 8 → 1.03 × 600 × 2.08 ÷ 36.7 = 35 kW.
Exam trap. Absolute pressures and Q in m³/HOUR in this book formula.

Isothermal efficiency

= Isothermal power ÷ Actual measured input power × 100
Symbols · units
SymbolskW
Answer unit%
Book topicIsothermal efficiency
compressorreceiverdryerpipe → usersleakload Tunload tkW

Where each value sits: kW → input kW, isothermal kW, SPC

What it means

Ideal power divided by what the compressor and motor actually draw — the reported compressor efficiency (typically 60–70 %).

Worked example. 35 kW ideal ÷ 55 kW actual = 64 %.
Exam trap. It is lower than adiabatic efficiency for the same machine — the book warns about comparing vendors' numbers.

Free air delivery by pump-up test

Q = [(P₂ − P₁) ÷ P₀] × V ÷ T
Symbols · units
SymbolsP₂ final, P₁ initial, P₀ atmospheric (kg/cm² abs); V = receiver + pipe volume (m³); T = time (min)
Answer unitm³/min
Book topicCapacity assessment
compressorreceiverdryerpipe → usersleakload Tunload tP₂P₀T

Where each value sits: P₂ → receiver V, P₁ → P₂, time T · P₁ → receiver V, P₁ → P₂, time T · P₀ → P₁ intake, P₂ delivery, r = P₂/P₁ · V → receiver V, P₁ → P₂, time T · T → T load, t unload

What it means

Shop-floor capacity test: isolate the receiver, time how long the compressor takes to raise its pressure from P₁ to P₂; the air delivered is the receiver volume times the pressure rise in atmospheres, per minute.

Worked example. V 5 m³, P₂ 8 kg/cm² a, P₁ 1 kg/cm² a, P₀ 1.03, T 5 min → (7/1.03) × 5 ÷ 5 = 6.8 m³/min.
Exam trap. Use ABSOLUTE pressures and include the pipe volume up to the isolation valve.

Leakage % (load–unload test)

= T ÷ (T + t) × 100
Symbols · units
SymbolsT = load (on) time, t = unload (off) time — same units
Answer unit%
Book topicLeakage test
compressorreceiverdryerpipe → usersleakload Tunload tT

Where each value sits: T → T load, t unload · t → T load, t unload

▶ Try it: Compressed air: load and unload times → leakage
green = loaded (replacing leaked air) · grey = unloaded
What it means

With no consumers connected, the compressor still loads periodically to replace leaked air; the fraction of time it spends loaded is the leakage fraction.

Worked example. Load 1.5 min, unload 10.5 min → 1.5/12 = 12.5 %. 200 cfm, load 10 s / unload 20 s → 67 cfm leakage (2023).
Exam trap. T (load) on top, T + t below.

Leakage quantity

q = Q × T ÷ (T + t)
Symbols · units
SymbolsQ = compressor capacity (m³/min)
Answer unitm³/min
Book topicLeakage test
compressorreceiverdryerpipe → usersleakload Tunload tQ

Where each value sits: Q → FAD Q, displacement

▶ Try it: Compressed air: load and unload times → leakage
green = loaded (replacing leaked air) · grey = unloaded
What it means

Leakage in flow units = compressor capacity × leakage fraction.

Worked example. 500 cfm × 0.125 = 62.5 cfm.
Exam trap. Same units as the capacity.

Specific power consumption

= Power (kW) ÷ FAD (m³/min)
Symbols · units
SymbolskW, m³/min
Answer unitkW per m³/min
Book topicPerformance
compressorreceiverdryerpipe → usersleakload Tunload tkWm³/min

Where each value sits: kW → input kW, isothermal kW, SPC · m³/min → FAD Q, displacement

▶ Try it: Chiller: flow and temperature drop of chilled water → tons of refrigeration
Evaporator
What it means

kW per unit of air delivered — the efficiency benchmark of a compressed-air system (typical 0.15–0.20 kW/cfm... in book units ≈ 6–8 kW per m³/min).

Worked example. 370 kW ÷ 2,392 m³/min... (book: 0.155 kW/m³).
Exam trap. Keep kW and flow in the same basis (per minute or per hour).

Power wasted in leakage

= Leakage quantity × Specific power consumption
Symbols · units
Symbolsm³/min × kW per m³/min
Answer unitkW
Book topicLeakage test
compressorreceiverdryerpipe → usersleakload Tunload tm³/min

Where each value sits: m³/min → input kW, isothermal kW, SPC

What it means

Leaked air cost you the power to compress it: leakage flow × specific power.

Worked example. 62.5 cfm × 0.18 kW/cfm = 11 kW, ≈ 88,000 kWh/yr.
Exam trap. Every 1 bar over-pressure also costs 6–7 % more power.

Gas law (air expansion / compression)

P₁ V₁ ÷ T₁ = P₂ V₂ ÷ T₂
Symbols · units
Symbolsabsolute pressure; volume; temperature in K
Answer unit—
Book topicPipe & receiver sizing
compressorreceiverdryerpipe → usersleakload Tunload tabsolutevolumetemperature

Where each value sits: absolute → P₁ intake, P₂ delivery, r = P₂/P₁ · volume → receiver V, P₁ → P₂, time T · temperature → T load, t unload

What it means

Relates pressure, volume and temperature of the same air at two states — used to convert free air to line-pressure volume for pipe sizing.

Worked example. 6 m³ of free air at 1 atm → at 8 atm abs and same T: 0.75 m³.
Exam trap. Absolute pressure and Kelvin temperature only.

Compressed air pipe diameter

Q = (π ÷ 4) × D² × v → D = √(4Q ÷ πv)
Symbols · units
SymbolsQ = flow at line pressure (m³/s), v = air velocity (m/s)
Answer unitm
Book topicPipe sizing
compressorreceiverdryerpipe → usersleakload Tunload tQv

Where each value sits: Q → FAD Q, displacement · v → receiver V, P₁ → P₂, time T

What it means

Choose the pipe so the air (at line pressure) moves at 6–10 m/s; faster means high pressure drop.

Worked example. 500 cfm FAD (0.236 m³/s) at 7 kg/cm² abs → 0.034 m³/s at line pressure; at 6 m/s area 0.0056 m² → D ≈ 85 mm (2023 S-5 pattern).
Exam trap. Convert FAD to volume at LINE pressure first (÷ pressure ratio).

Air receiver size

V = 1/10 to 1/6 × compressor output
Symbols · units
Symbolsoutput in m³/min
Answer unitm³
Book topicAir receivers
compressorreceiverdryerpipe → usersleakload Tunload toutput

Where each value sits: output → capacity, rated vs actual

What it means

Storage that smooths demand peaks and reduces load/unload cycling; IS 7938 rule of thumb.

Worked example. 10 m³/min compressor → 1–1.7 m³ receiver.
Exam trap. Bigger is not always better: too large delays pressure recovery.

Capacity shortfall of a compressor

= (Rated − Actual FAD) ÷ Rated × 100
Symbols · units
Symbolsm³/min
Answer unit%
Book topicCapacity assessment
compressorreceiverdryerpipe → usersleakload Tunload tm³/min

Where each value sits: m³/min → FAD Q, displacement

What it means

Compares tested FAD with the rated value; a shortfall above ~10 % means worn valves, rings or leaks and calls for overhaul.

Worked example. Rated 15, actual 13.2 m³/min → 12 %.
Exam trap. Compare on the same pressure and temperature basis.

m³/min to cfm

cfm = m³/min × 35.31
Symbols · units
Symbolsm³/min
Answer unitcfm
Book topicUnits
compressorreceiverdryerpipe → usersleakload Tunload tm³/min

Where each value sits: m³/min → FAD Q, displacement

What it means

Unit bridge between the book's SI values and nameplates in cfm.

Worked example. 10 m³/min = 353 cfm.
Exam trap. Divide by 35.31 to go the other way.

Leakage test — load/unload timeline

time (no consumers connected) load Tunload tload Tunload t The compressor loads only to replace leaked air → leakage % = T ÷ (T + t) × 100

FAD pump-up test

Receiver V m³valve closed compressor time T to raiseP₁ → P₂ (abs) FAD Q = [(P₂ − P₁) ÷ P₀] × V ÷ T m³/min (all pressures absolute)
Definitions the exam asks
Types of compressors
Positive displacement (reciprocating, screw, vane) and dynamic (centrifugal). Centrifugal machines do not use load/unload capacity control.
Intercooling
Cooling air between stages reduces its volume so the next stage does less work — the main reason multi-stage compression saves power.
Air dryers
Refrigerated (dew point +3 °C, cheapest power), heatless desiccant (uses 15–20 % purge air, highest cost), heat-of-compression (lowest operating cost); adsorption dryers use activated alumina / silica gel / molecular sieve.
Pressure settings
Every 1 bar reduction in delivery pressure saves 6–7 % power; each 4 °C rise in intake temperature costs ~1 %.
Leakage benchmarks
Well-maintained system < 10 % of capacity; badly maintained 20–30 %.
Verified videos for this chapter (YouTube)
FAD Pump-Up Test Method — Part 8 Air Leakage · Les DruivenLeakage Quantification Test — How to Check for Air Leaks in Five Simple Steps · Compressed Air ControlsAir Dryers Comparison — How to calculate your compressed air leaks cost - VPInstruments · PNEUMSYS ADVANCE ENERGY SOLUTIONS

Chapter 4 · HVAC and Refrigeration System

~23 marks (top chapter): TR, COP, kW/TR numericals every year; VCR vs VAM, refrigerants, psychrometry and ventilation.

Water-cooled centrifugal chiller — evaporator and condenser shells with the compressor on top
Water-cooled centrifugal chiller — evaporator and condenser shells with the compressor on topPhoto: P199 · Public domain · source
Sling psychrometer — wet-bulb and dry-bulb thermometers give relative humidity
Sling psychrometer — wet-bulb and dry-bulb thermometers give relative humidityPhoto: User:CambridgeBayWeather · Public domain · source

Refrigeration load from chilled water

TR = Q × Cp × (Ti − To) ÷ 3024
Symbols · units
SymbolsQ = coolant flow (kg/hr), Cp (kcal/kg °C), Ti, To = inlet, outlet temperature (°C)
Answer unitTR
Book topicPerformance assessment
condenserevaporator / chillercompressorWexpansion valvechilled water in Tiout Toheat to cooling towerQ

Where each value sits: Q → Q flow kg/hr, Cp, Ti, To → TR · Cp → Q flow kg/hr, Cp, Ti, To → TR · Ti → Q flow kg/hr, Cp, Ti, To → TR · To → Q flow kg/hr, Cp, Ti, To → TR · outlet: outlet temperature (°C)

▶ Try it: Chiller: flow and temperature drop of chilled water → tons of refrigeration
Evaporator
What it means

Heat removed from the chilled water = flow × specific heat × temperature drop; divided by 3,024 to give tons of refrigeration.

Worked example. 20 m³/hr cooled 17 → 10 °C: 20,000 × 1 × 7 ÷ 3,024 = 46.3 TR.
Exam trap. Flow in kg/HOUR (m³/hr × 1000); 3,024 kcal/hr per TR.

Refrigeration load from air side (AHU / FCU)

TR = Q × ρ × (h in − h out) ÷ 3024
Symbols · units
SymbolsQ = air flow (m³/hr), ρ = air density (kg/m³), h = enthalpy (kcal/kg)
Answer unitTR
Book topicPerformance assessment
condenserevaporator / chillercompressorWexpansion valvechilled water in Tiout Toheat to cooling towerQρ

Where each value sits: Q → Q flow kg/hr, Cp, Ti, To → TR · ρ → air flow, ρ, h in/out, ACH, L×B×H · h → air flow, ρ, h in/out, ACH, L×B×H

What it means

Same idea on the air side: air mass flow × enthalpy drop across the coil, read from the psychrometric chart.

Worked example. 10,800 m³/hr × 1.2 kg/m³ × (h_in − h_out) ÷ 3,024.
Exam trap. Use enthalpy (total heat) for air, not just temperature — latent heat of moisture matters.

Specific power consumption

kW/TR = Power input (kW) ÷ TR
Symbols · units
SymbolskW, TR
Answer unitkW/TR
Book topicPerformance assessment
condenserevaporator / chillercompressorWexpansion valvechilled water in Tiout Toheat to cooling towerkWTR

Where each value sits: kW → power input kW, W · TR → Q flow kg/hr, Cp, Ti, To → TR

▶ Try it: Chiller: flow and temperature drop of chilled water → tons of refrigeration
Evaporator
What it means

The benchmark of a refrigeration plant: kW drawn per ton produced. Good centrifugal chillers ≈ 0.6–0.7 kW/TR; reciprocating ≈ 1.0–1.2.

Worked example. Compressor 10.69 kW for 8.07 TR → 1.32 kW/TR (book example).
Exam trap. Lower kW/TR is better; it is the inverse of COP (× 3.51).

Overall kW/TR of a chilled-water plant

= Compressor + Chilled-water pump + Condenser-water pump + Cooling-tower fan kW/TR
Symbols · units
Symbolseach in kW/TR
Answer unitkW/TR
Book topicPerformance assessment
condenserevaporator / chillercompressorWexpansion valvechilled water in Tiout Toheat to cooling towereach

Where each value sits: each → COP, kW/TR, EER

What it means

Add the pumps and cooling-tower fan to the compressor — the plant benchmark, not just the chiller's.

Worked example. (10.69 + 4.86 + 0.87) ÷ 8.07 = 2.03 kW/TR (book).
Exam trap. The exam sometimes asks for compressor kW/TR only — read which.

Coefficient of performance

COP = Refrigeration effect ÷ Power input
Symbols · units
Symbolsboth in the same units (kW ÷ kW)
Answer unitno unit
Book topicCOP
condenserevaporator / chillercompressorWexpansion valvechilled water in Tiout Toheat to cooling towerboth

Where each value sits: both → power input kW, W

▶ Try it: Chiller: flow and temperature drop of chilled water → tons of refrigeration
Evaporator
What it means

Cooling produced per unit of work input, both in the same units. Higher COP = more efficient. Typical VCR 3–5; single-effect VAM ≈ 0.65–0.7.

Worked example. Cooling 3.517 kW per TR at 1.7 kW/TR → COP 2.07 (2018/2021).
Exam trap. Same units top and bottom (kW ÷ kW, or kcal ÷ kcal).

COP from kW/TR

COP = 3.51 ÷ (kW/TR)
Symbols · units
Symbols1 TR = 3.51 kW
Answer unitno unit
Book topicCOP
condenserevaporator / chillercompressorWexpansion valvechilled water in Tiout Toheat to cooling tower1 TR

Where each value sits: 1 TR → Q flow kg/hr, Cp, Ti, To → TR

▶ Try it: Chiller: flow and temperature drop of chilled water → tons of refrigeration
Evaporator
What it means

Because 1 TR = 3.51 kW of cooling, COP is simply 3.51 divided by the kW/TR.

Worked example. 0.7 kW/TR → COP 5.0.
Exam trap. Use 3.51 (kW), not 3,024 (kcal/hr) with kW.

Carnot COP

COP = Te ÷ (Tc − Te)
Symbols · units
SymbolsTe = evaporator, Tc = condenser temperature (K = °C + 273)
Answer unitno unit
Book topicCOP
condenserevaporator / chillercompressorWexpansion valvechilled water in Tiout Toheat to cooling towerTeTc

Where each value sits: Te → Te evaporator · Tc → heat rejected, Tc

What it means

The theoretical best for the two temperatures; shows why a HIGHER evaporator temperature and LOWER condenser temperature raise efficiency (≈ 2–3 % per °C).

Worked example. Te 5 °C (278 K), Tc 40 °C (313 K) → 278 ÷ 35 = 7.9.
Exam trap. Kelvin — add 273 to both.

Energy efficiency ratio (star label)

EER = Refrigeration effect (W) ÷ Power input (W)
Symbols · units
SymbolsW, W
Answer unitW/W
Book topicRoom AC labelling
condenserevaporator / chillercompressorWexpansion valvechilled water in Tiout Toheat to cooling towerW

Where each value sits: W → power input kW, W · W → power input kW, W

What it means

COP expressed in watts of cooling per watt of input (or BTU/hr per W in older labels); the basis of the BEE star rating for room ACs.

Worked example. 5 TR unit delivering 4 TR cooling with EER 2.9... (2018/2021 objective 4.84).
Exam trap. EER and COP are the same ratio when both sides are in watts.

Heat rejected in the condenser

= Refrigeration effect + Compressor work
Symbols · units
SymbolsTR × 3024 + kW × 860 (kcal/hr)
Answer unitkcal/hr
Book topicRefrigeration cycle
condenserevaporator / chillercompressorWexpansion valvechilled water in Tiout Toheat to cooling towerTR

Where each value sits: TR → Q flow kg/hr, Cp, Ti, To → TR

What it means

The condenser must dump the heat taken from the room PLUS the compressor's work — always more than the cooling effect.

Worked example. 100 TR at COP 4: cooling 302,400 kcal/hr + work 25 kW × 860 = 21,500 → 323,900 kcal/hr to the cooling tower.
Exam trap. Condenser heat > evaporator heat, always.

Heat delivered by a heat pump

= Qe + W
Symbols · units
SymbolsQe = waste heat taken in (kW), W = compressor work (kW)
Answer unitkW
Book topicHeat pumps
condenserevaporator / chillercompressorWexpansion valvechilled water in Tiout Toheat to cooling towerQeW

Where each value sits: Qe → Q flow kg/hr, Cp, Ti, To → TR · W → power input kW, W

What it means

A heat pump is a refrigerator used for its hot side: it delivers the waste heat it absorbed plus the compressor work, so heating COP is always > 1.

Worked example. Absorbs 100 kW at 20 kW work → delivers 120 kW (COP 6 heating).
Exam trap. Heating COP = cooling COP + 1.

Ventilation rate

Q = L × B × H × ACH
Symbols · units
SymbolsL, B, H = room size (m), ACH = air changes per hour
Answer unitm³/hr
Book topicVentilation
condenserevaporator / chillercompressorWexpansion valvechilled water in Tiout Toheat to cooling towerL

Where each value sits: L → air flow, ρ, h in/out, ACH, L×B×H · B → air flow, ρ, h in/out, ACH, L×B×H · H → air flow, ρ, h in/out, ACH, L×B×H · ACH → air flow, ρ, h in/out, ACH, L×B×H

What it means

Air changes per hour times the room volume gives the fan duty for ventilating a room (compressor rooms 10–20 ACH, engine rooms 20).

Worked example. 15 × 10 × 4 m room at 10 ACH = 6,000 m³/hr (book); 15 × 10 × 4 at 20 ACH = 12,000 m³/hr (2018/2022 objective).
Exam trap. ACH is per HOUR; divide by 3,600 for m³/s.

Water added in humidification

m = V × ρ × (w₂ − w₁)
Symbols · units
SymbolsV = air flow (m³/hr), ρ (kg/m³), w = specific humidity (kg/kg dry air)
Answer unitkg/hr
Book topicHumidification
condenserevaporator / chillercompressorWexpansion valvechilled water in Tiout Toheat to cooling towerVρw

Where each value sits: V → Q flow kg/hr, Cp, Ti, To → TR · ρ → air flow, ρ, h in/out, ACH, L×B×H · w → power input kW, W

What it means

Spraying water into air raises its moisture content; the water needed is the air mass flow times the rise in specific humidity.

Worked example. 3,000 m³/h × 1.2 × (0.0062 − 0.002) = 15.1 kg/h (book textile example).
Exam trap. Humidity is per kg of DRY air; DBT falls during adiabatic humidification.

Condenser water flow norm

≈ 0.91 m³/hr per TR (4 gpm per TR)
Symbols · units
SymbolsTR
Answer unitm³/hr per TR
Book topicPerformance assessment
condenserevaporator / chillercompressorWexpansion valvechilled water in Tiout Toheat to cooling towerTR

Where each value sits: TR → Q flow kg/hr, Cp, Ti, To → TR

What it means

Design rule: about 0.91 m³/hr (4 US gpm) of cooling water per ton — used to check whether the condenser is starved of water.

Worked example. 250 TR chiller → ≈ 228 m³/hr condenser water.
Exam trap. This is a check figure, not a formula to derive.

Vapour-compression cycle

Condenser (heat OUT) Evaporator (heat IN) Compressorwork W Expansion valveh = constant Heat rejected at condenser = cooling effect + compressor work. COP = cooling ÷ W. Enthalpy stays constant across the expansion valve.

Psychrometric chart basics

dry-bulb temperaturemoisture content saturation line (RH 100 %) air at DBT, some RH adiabatic humidification (air washer): DBT ↓, RH ↑, enthalpy constant sensible heating: RH ↓
Definitions the exam asks
Vapour compression vs absorption
VCR: compressor (electrical) drives the cycle, COP 3–5. VAM: generator (heat) drives it with absorbent LiBr or water-ammonia, COP 0.65–1.2, uses waste heat/steam. Ammonia is the refrigerant common to both; 'generator' is the VAM part that is NOT in VCR; 'absorber' likewise.
Refrigerants
CFCs (R-11, R-12) phased out for ozone; HCFC R-22 being phased out; HFC R-134a; natural: ammonia (R-717), CO₂, hydrocarbons.
Chilled-water temperature
Raising the chilled-water leaving temperature by 1 °C improves compressor efficiency ≈ 3 %; lowering condenser temperature does the same.
Psychrometry terms
DBT, WBT, RH, dew point, specific humidity, enthalpy; when DBT = WBT the air is saturated.
Star labelling of room ACs
Based on EER (W/W) at standard test conditions; higher EER = more stars.
Verified videos for this chapter (YouTube)
VCR 4-Stage Cycle vs. VAM — Refrigeration Capacity, kW/TR, Coefficient of Performance #COP · Nishant Bajpai's FinTech EducationPsychrometrics & Air Washers — What is a Refrigeration Ton + CALCULATIONS chiller hvac btu kw · The Engineering MindsetChiller Efficiency & Fouling — COP and KW per Ton · VRF Wizard

Chapter 5 · Fans and Blowers

~11 marks: fan laws (power ∝ N³) and static-efficiency numericals; fan types, dampers vs VFD, ASME classification.

Industrial centrifugal fan on its motor base
Industrial centrifugal fan on its motor basePhoto: SAF · CC BY-SA 4.0 · source
Axial-flow fan — air enters and leaves along the shaft with no change of direction
Axial-flow fan — air enters and leaves along the shaft with no change of directionPhoto: Bobbie4 (talk) · Public domain · source
Pitot-static tube — measures velocity pressure for duct flow
Pitot-static tube — measures velocity pressure for duct flowPhoto: Z22 · CC BY-SA 3.0 · source

ASME specific ratio

SR = Discharge pressure ÷ Suction pressure
Symbols · units
Symbolsabsolute pressures
Answer unitno unit (fan ≤ 1.11, blower 1.11–1.20, compressor > 1.20)
Book topicFan / blower / compressor
inlet duct (suction −)outlet duct (+)motorbeltpitot / manometerabsolute

Where each value sits: absolute → duct area A

What it means

Fans, blowers and compressors are classified by the pressure ratio they develop, not by their construction.

Worked example. Discharge 1.10 bar abs ÷ suction 1.0 → 1.10: a fan.
Exam trap. Fan ≤ 1.11, blower 1.11–1.20, compressor > 1.20 (2013/2017/2022 objective).

Fan law – flow

Q₂ ÷ Q₁ = N₂ ÷ N₁
Symbols · units
SymbolsN = fan speed (rpm)
Answer unitm³/s (same as Q₁)
Book topicFan laws
inlet duct (suction −)outlet duct (+)motorbeltpitot / manometerN

Where each value sits: N → speed N

▶ Try it: Fan laws: slow the fan down — power falls with the CUBE of speed
fan speed N flow pressure power
What it means

Flow is directly proportional to speed: 10 % less speed = 10 % less air.

Worked example. 800 → 600 rpm: flow falls to 75 %.
Exam trap. This is the only linear fan law.

Fan law – pressure

SP₂ ÷ SP₁ = (N₂ ÷ N₁)²
Symbols · units
SymbolsN (rpm)
Answer unitmmWC
Book topicFan laws
inlet duct (suction −)outlet duct (+)motorbeltpitot / manometerN

Where each value sits: N → speed N

▶ Try it: Fan laws: slow the fan down — power falls with the CUBE of speed
fan speed N flow pressure power
What it means

Pressure rises with the square of speed.

Worked example. Speed × 1.1 → pressure × 1.21.
Exam trap. Square, not cube, for pressure.

Fan law – power

kW₂ ÷ kW₁ = (N₂ ÷ N₁)³
Symbols · units
SymbolsN (rpm)
Answer unitkW
Book topicFan laws
inlet duct (suction −)outlet duct (+)motorbeltpitot / manometerN

Where each value sits: N → speed N

▶ Try it: Fan laws: slow the fan down — power falls with the CUBE of speed
fan speed N flow pressure power
What it means

Power rises with the CUBE of speed — the whole case for VFDs on fans: 20 % less flow needs only 51 % of the power.

Worked example. 16 kW at 800 rpm → at 600 rpm: 16 × (600/800)³ = 6.75 kW (2018/2021/2024). 52 kW at 49 Hz → at 47 Hz: 52 × (47/49)³ = 45.9 kW.
Exam trap. Cube the speed RATIO; a damper does not follow this law — only speed change does.

Total pressure

TP = SP + VP
Symbols · units
SymbolsSP = static, VP = velocity pressure (mmWC)
Answer unitmmWC
Book topicFan performance
inlet duct (suction −)outlet duct (+)motorbeltpitot / manometerSPVP

Where each value sits: SP → static pressure outlet · VP → velocity pressure Δp, Cp

What it means

Total = static (pushes on the duct walls) + velocity (from the moving air).

Worked example. SP 40 mmWC, VP 5 → TP 45.
Exam trap. Velocity pressure is what a pitot tube measures as the difference between total and static ports.

Air velocity from pitot-tube reading

v = Cp × √(2 × 9.81 × Δp × γ) ÷ γ
Symbols · units
SymbolsCp = pitot coefficient (≈ 0.85), Δp = velocity pressure (mmWC), γ = gas density (kg/m³)
Answer unitm/s
Book topicFlow measurement
inlet duct (suction −)outlet duct (+)motorbeltpitot / manometerCpγ

Where each value sits: Cp → velocity pressure Δp, Cp · Δp → velocity pressure Δp, Cp · γ → gas density γ, T, M

What it means

Convert the velocity-pressure reading on a manometer into air speed, corrected for the pitot coefficient and the gas density.

Worked example. Cp 0.9, Δp 47 mmWC, γ 1.135 → 0.9 × √(2 × 9.81 × 47 × 1.135)/1.135 = 25.6 m/s (book example).
Exam trap. Density at the FLOW temperature, not at 0 °C.

Gas density (ideal gas)

γ = P × M ÷ (R × T)
Symbols · units
SymbolsP = absolute pressure (mmWC), M = mol. weight (air 28.92), R = 847.84 mmWC·m³/kg-mole·K, T (K)
Answer unitkg/m³
Book topicFlow measurement
inlet duct (suction −)outlet duct (+)motorbeltpitot / manometerP

Where each value sits: P → gas density γ, T, M · M → gas density γ, T, M · R → gas density γ, T, M · m³/kg-mole → gas density γ, T, M · K: K · T → gas density γ, T, M

What it means

Density falls as the gas gets hotter or the pressure drops; needed before velocity and mass-flow calculations for hot flue gas.

Worked example. Air at 10,330 mmWC, 311 K: 10,330 × 28.92 ÷ (847.84 × 311) = 1.133 kg/m³.
Exam trap. Absolute pressure in mmWC and T in kelvin with R = 847.84.

Air density at t °C

γ = 1.293 × 273 ÷ (273 + t)
Symbols · units
Symbols1.293 kg/m³ at 0 °C; t (°C)
Answer unitkg/m³
Book topicFlow measurement
inlet duct (suction −)outlet duct (+)motorbeltpitot / manometert

Where each value sits: 1.293: 1.293 kg/m³ at 0 °C · t → gas density γ, T, M

What it means

Quick correction from the standard 1.293 kg/m³ at 0 °C.

Worked example. At 38 °C: 1.293 × 273/311 = 1.135 kg/m³.
Exam trap. Kelvin ratio, with 273 on top.

Molecular weight of flue gas (dry)

M = (%CO₂ × 44 + %O₂ × 32 + %CO × 28 + %N₂ × 28) ÷ 100
Symbols · units
Symbolsgas analysis in % (dry basis)
Answer unitkg/kg-mole
Book topicFlow measurement
inlet duct (suction −)outlet duct (+)motorbeltpitot / manometer%CO₂ %O₂ %CO %N₂

Where each value sits: %CO₂ %O₂ %CO %N₂ → gas density γ, T, M · M → gas density γ, T, M

What it means

Weighted average of the gases in the flue-gas analysis; used in the density formula for boiler ID/FD fans.

Worked example. 12 % CO₂, 6 % O₂, 82 % N₂ → 0.12×44 + 0.06×32 + 0.82×28 = 30.2.
Exam trap. Dry basis; water vapour is excluded.

Volume flow in a duct

Q = Velocity × Duct area
Symbols · units
Symbolsm/s × m²
Answer unitm³/s
Book topicFlow measurement
inlet duct (suction −)outlet duct (+)motorbeltpitot / manometerm/s

Where each value sits: m/s → gas density γ, T, M

What it means

Average velocity from a pitot traverse times the duct cross-section.

Worked example. 25.6 m/s × 0.5 m² = 12.8 m³/s.
Exam trap. Use the average of several traverse points, not the centre-line reading.

Fan mechanical (total) efficiency

η = Q × TP ÷ (102 × Shaft kW) × 100
Symbols · units
SymbolsQ (m³/s), TP = total pressure (mmWC), shaft power (kW)
Answer unit%
Book topicFan efficiency
inlet duct (suction −)outlet duct (+)motorbeltpitot / manometerQTPshaft

Where each value sits: Q → air flow Q · TP → static pressure outlet · shaft → motor kW, η motor

What it means

How well the shaft power becomes air power, counting both static and velocity pressure.

Worked example. 12.65 m³/s × 210 mmWC ÷ (102 × 67.65 kW) = 38.5 %.
Exam trap. 102 = 1000 ÷ 9.81, converting m³/s × mmWC to kW.

Fan static efficiency

η = Q × SP ÷ (102 × Shaft kW) × 100
Symbols · units
SymbolsQ (m³/s), SP = static pressure rise (mmWC), shaft power (kW)
Answer unit%
Book topicFan efficiency
inlet duct (suction −)outlet duct (+)motorbeltpitot / manometerQSPshaft

Where each value sits: Q → air flow Q · SP → static pressure outlet · shaft → motor kW, η motor

What it means

Same, but counting only the static pressure rise — the usual figure quoted, and what the exam asks (2019 L-1, 2021 S-7).

Worked example. 12.65 × (185 − (−20)) ÷ (102 × 67.65) = 37.6 % (book example).
Exam trap. Inlet static pressure is NEGATIVE (suction): 185 − (−20) = 205.

Power input to fan shaft

= Motor input kW × η motor (× η belt drive)
Symbols · units
SymbolskW; η as fractions
Answer unitkW
Book topicFan efficiency
inlet duct (suction −)outlet duct (+)motorbeltpitot / manometerkW

Where each value sits: kW → motor kW, η motor · η: η as fractions

What it means

Motor input kW is not fan input: subtract the motor loss and, for belt drives, the belt loss.

Worked example. 75 kW input × 0.97 (motor) × 0.93 (belt) = 67.65 kW (book).
Exam trap. Use shaft power in the efficiency formula, never motor input.

Static pressure rise across the fan

= SP outlet − SP inlet
Symbols · units
Symbolsinlet (suction) pressure is negative (mmWC)
Answer unitmmWC
Book topicFan performance
inlet duct (suction −)outlet duct (+)motorbeltpitot / manometerinlet

Where each value sits: inlet → static pressure inlet

What it means

The pressure the fan adds: outlet static minus inlet static, remembering the inlet is usually below atmosphere.

Worked example. Outlet +10, inlet −230 → 240 mmWC (book ID fan).
Exam trap. Two negatives: subtracting a negative inlet ADDS.

The three fan laws

speed N (%) flow ∝ N pressure ∝ N² power ∝ N³ 80 % speed → 51 % power

Static pressure rise across a fan

inlet duct SP = −20 mmWC FAN outlet duct SP = +185 mmWC Static rise across the fan = 185 − (−20) = 205 mmWC · η static = Q × 205 ÷ (102 × shaft kW) Total pressure = static + velocity pressure; the pitot tube reads velocity pressure → v = Cp √(2·9.81·Δp/γ)
Definitions the exam asks
Fan types
Centrifugal: radial (dust), forward-curved (low pressure, HVAC), backward-curved/inclined (non-overloading, most efficient). Axial: propeller, tube-axial, vane-axial — air does not change direction.
System resistance
Depends on ducts, bends, dampers, pickups; ∝ flow². Larger ducts and fewer bends lower it.
Flow control
Damper (wastes energy), inlet guide vanes (better, modest range), variable speed (best — power ∝ N³), pulley change (cheap, permanent).
Non-overloading fan
Backward-curved fans — power peaks then falls with flow, so the motor cannot be overloaded.
Verified videos for this chapter (YouTube)
ASME Specific Ratio & Fan Types — Three Key Fan Laws Explained: Airflow vs. Static Pressure vs. Horsepower · The New York Blower Company

Chapter 6 · Pumps and Pumping System

~18 marks: pump power (ρgQH), efficiency and affinity/impeller-trimming numericals; throttling vs VFD; NPSH and cavitation.

Close-coupled centrifugal pumps with pressure gauges on suction and discharge
Close-coupled centrifugal pumps with pressure gauges on suction and dischargePhoto: Saud · CC BY-SA 4.0 · source
Large centrifugal pump — impeller casing (volute) and suction inlet
Large centrifugal pump — impeller casing (volute) and suction inletPhoto: Bernard S. Janse · CC BY 2.5 · source

Hydraulic power

Ph = Q × (hd − hs) × ρ × g ÷ 1000
Symbols · units
SymbolsQ (m³/s), hd = discharge head, hs = suction head (m), ρ (kg/m³), g = 9.81 m/s²
Answer unitkW
Book topicPump power
sumptankmotorQhdhsρg

Where each value sits: Q → pipe: flow Q · hd → discharge head hd · hs → suction head hs · ρ → liquid ρ · g → g = 9.81 m/s²

▶ Try it: Pump: change flow and head — watch the water rise and the power change
sump pump H shaft power → motorhydraulic kW
What it means

The power actually given to the water: how much flows (Q) times how high it is lifted (head) times the weight of water. This is the useful output of the pump.

Worked example. Q 0.0888 m³/s, H 32 m, water: 0.0888 × 32 × 1000 × 9.81 ÷ 1000 = 27.9 kW (book example).
Exam trap. Q in m³/SECOND (m³/hr ÷ 3600); head in metres of the liquid pumped.

Pump shaft power

Ps = Ph ÷ η pump
Symbols · units
SymbolskW; η as fraction
Answer unitkW
Book topicPump power
sumptankmotorPhη pumpPs

Where each value sits: Ph → hydraulic power Ph · η pump → pump η · Ps → shaft power Ps

▶ Try it: Pump: change flow and head — watch the water rise and the power change
sump pump H shaft power → motorhydraulic kW
What it means

What the pump needs at its shaft; larger than hydraulic power because of the pump's own losses.

Worked example. 27.9 kW ÷ 0.61 = 45.7 kW.
Exam trap. Divide by efficiency (a fraction), do not multiply.

Motor input power

= Ps ÷ η motor
Symbols · units
SymbolskW; η as fraction
Answer unitkW
Book topicPump power
sumptankmotorPsη motor

Where each value sits: Ps → shaft power Ps · η motor → motor η, input kW · input kW → motor η, input kW

What it means

What the electricity meter sees: shaft power plus the motor's losses.

Worked example. 45.7 ÷ 0.9 = 50.7 kW.
Exam trap. Two efficiencies in series: hydraulic ÷ η_pump ÷ η_motor.

Pump efficiency

η pump = Ph ÷ Ps × 100
Symbols · units
SymbolskW
Answer unit%
Book topicPump power
sumptankmotorPhPsη

Where each value sits: Ph → hydraulic power Ph · Ps → shaft power Ps · η → pump η

▶ Try it: Pump: change flow and head — watch the water rise and the power change
sump pump H shaft power → motorhydraulic kW
What it means

Useful water power divided by the shaft power; measured in an audit from flow, head and motor kW (× motor efficiency).

Worked example. Hydraulic 27.9 kW; motor 50.7 kW at 90 % → shaft 45.6 → η = 61 % (book). 2024 S-6: 5 m suction + 30 m discharge, 150 m³/hr, 18 kW motor at 85 % → 15.3 kW shaft → η ≈ 93 %... check numbers in the paper.
Exam trap. Use SHAFT power (motor kW × motor η), not motor input, or you understate efficiency.

Head from a pressure-gauge reading (water)

Head (m) = Pressure (kg/cm²) × 10
Symbols · units
Symbolskg/cm²
Answer unitm
Book topicPump head
sumptankmotorkg/cm²

Where each value sits: kg/cm² → pressure gauge kg/cm²

What it means

A pressure gauge in kg/cm² converts to metres of water column at about 10 m per kg/cm²; add suction lift (or subtract positive suction head) to get total head.

Worked example. Discharge 2.6 kg/cm² = 26 m; water 4 m BELOW pump centreline → total head 30 m (2013 exam). 3.0 kg/cm² with +5 m positive suction → 30 − 5 = 25 m (2024).
Exam trap. Suction lift ADDS to head; positive suction head SUBTRACTS.

Affinity law – flow and speed

Q₁ ÷ Q₂ = N₁ ÷ N₂
Symbols · units
SymbolsN = speed (rpm)
Answer unitm³/hr
Book topicAffinity laws
sumptankmotorN

Where each value sits: N → speed N, impeller D

What it means

Flow moves in step with speed.

Worked example. 3000 → 1500 rpm: 100 m³/hr → 50 (book).
Exam trap. Linear — the only one.

Affinity law – head and speed

H₁ ÷ H₂ = (N₁ ÷ N₂)²
Symbols · units
SymbolsN (rpm)
Answer unitm
Book topicAffinity laws
sumptankmotorN

Where each value sits: N → speed N, impeller D

What it means

Head varies with the square of speed.

Worked example. Speed halved → head 100 m → 25 m (book).
Exam trap. Square.

Affinity law – power and speed

kW₁ ÷ kW₂ = (N₁ ÷ N₂)³
Symbols · units
SymbolsN (rpm)
Answer unitkW
Book topicAffinity laws
sumptankmotorN

Where each value sits: N → speed N, impeller D

▶ Try it: Fan laws: slow the fan down — power falls with the CUBE of speed
fan speed N flow pressure power
What it means

Power varies with the CUBE of speed — halving speed needs one-eighth of the power; two-thirds speed ≈ 30 %.

Worked example. 40 kW at 3000 rpm → 5 kW at 1500 rpm (book).
Exam trap. Cube the ratio of speeds, not the ratio of flows squared.

Impeller trimming – flow

Q₁ ÷ Q₂ = D₁ ÷ D₂
Symbols · units
SymbolsD = impeller diameter (mm)
Answer unitm³/hr
Book topicImpeller trimming
sumptankmotorD

Where each value sits: D → speed N, impeller D

What it means

Trimming the impeller diameter reduces flow in proportion — a one-time, cheap fix for an oversized pump that is throttled.

Worked example. Flow 150 → 110 m³/hr needs D = 230 × 110/150 = 169 mm (2018/2024 objective).
Exam trap. Trim only down to ~75 % of the original diameter; beyond that efficiency collapses.

Impeller trimming – head

H₁ ÷ H₂ = (D₁ ÷ D₂)²
Symbols · units
SymbolsD (mm)
Answer unitm
Book topicImpeller trimming
sumptankmotorD

Where each value sits: D → speed N, impeller D

What it means

Head falls with the square of the diameter ratio.

Worked example. D ratio 0.9 → head 81 %.
Exam trap. Square.

Impeller trimming – power

P₁ ÷ P₂ = (D₁ ÷ D₂)³
Symbols · units
SymbolsD (mm)
Answer unitkW
Book topicImpeller trimming
sumptankmotorD

Where each value sits: D → speed N, impeller D

What it means

Power falls with the cube of the diameter ratio — the saving from trimming.

Worked example. D ratio 0.9 → power 73 %.
Exam trap. Cube.

Friction head at a new flow

h₂ = h₁ × (Q₂ ÷ Q₁)²
Symbols · units
Symbolsfriction head (m) varies with the square of flow
Answer unitm
Book topicSystem curve
sumptankmotorfriction

Where each value sits: friction → pipe: flow Q

What it means

Pipe friction losses rise with the square of flow; static head (the lift) does not change. This is why the system curve is a parabola sitting on the static head.

Worked example. Friction 15 m at 100 m³/hr → at 80 m³/hr: 15 × 0.64 = 9.6 m; static 10 m stays 10 m (2011 objective).
Exam trap. Static head is constant; ONLY the friction part scales with Q².

Pump curve, system curve and speed control

flow Qhead H pump curve (full speed) pump at reduced speed (affinity) static head (constant) system curve: static + friction ∝ Q² operating point
Definitions the exam asks
System curve
Static head (constant) plus friction head (∝ Q²); the pump runs where its curve meets the system curve.
Throttling vs speed control
A throttled valve adds resistance and wastes the head; reducing speed moves the pump curve down — power falls with N³. Throttled > 30 % → trim impeller or fit a VFD.
NPSH and cavitation
Net positive suction head available must exceed the pump's required NPSH; otherwise vapour bubbles form and collapse (cavitation). Larger suction pipe, lower liquid temperature and lower suction lift raise NPSHa.
Pumps in series / parallel
Series adds head (shut-off head doubles for two identical pumps); parallel adds flow (shut-off head unchanged).
By-pass lines
Small by-pass lines protect the pump against overheating at very low or zero flow.

Chapter 7 · Cooling Tower

~13 marks: range/approach/effectiveness, evaporation, COC and blowdown numericals recur; L/G ratio and fill types.

Induced-draft cooling tower cells with fans on top
Induced-draft cooling tower cells with fans on topPhoto: Cenk Endustri · CC BY-SA 3.0 · source
Fill media inside a cooling tower — where water film meets the air
Fill media inside a cooling tower — where water film meets the airPhoto: SAF · CC BY-SA 4.0 · source
Natural-draft (hyperbolic) cooling tower seen from inside
Natural-draft (hyperbolic) cooling tower seen from insidePhoto: TJBlackwell · CC BY 3.0 · source

Range

= T₁ − T₂ (CW inlet hot − CW outlet cold)
Symbols · units
Symbolswater temperatures (°C)
Answer unit°C
Book topicPerformance
fillhot water in T₁cold out T₂air in (WBT)evaporation + driftblowdownmake-upT₁T₂range

Where each value sits: T₁ → T₁ hot water in · T₂ → T₂ cold water out · range → range = T₁ − T₂

▶ Try it: Cooling tower: move the temperatures — range, approach and effectiveness
What it means

How much the tower cools the water — set by the PROCESS heat load and flow, not by the tower.

Worked example. Hot 43 °C in, 35 °C out → range 8 °C.
Exam trap. Range is water-to-water.

Approach

= CW outlet (cold) temperature − Ambient wet-bulb temperature
Symbols · units
Symbols°C
Answer unit°C
Book topicPerformance
fillhot water in T₁cold out T₂air in (WBT)evaporation + driftblowdownmake-upT₂WBTapproach

Where each value sits: T₂ → T₂ cold water out · WBT → wet-bulb temperature · approach → approach = T₂ − WBT

▶ Try it: Cooling tower: move the temperatures — range, approach and effectiveness
What it means

How close the cold water gets to the air's wet-bulb temperature — the true measure of tower performance; lower approach = better (and bigger, costlier) tower.

Worked example. Cold water 32.2 °C, WBT 26.7 → approach 5.5 °C (book).
Exam trap. Approach uses the WET-bulb of the ambient air, not the dry-bulb, and not the inlet water.

Cooling tower effectiveness

= Range ÷ (Range + Approach) × 100
Symbols · units
Symbols°C
Answer unit%
Book topicPerformance
fillhot water in T₁cold out T₂air in (WBT)evaporation + driftblowdownmake-uprangeapproach

Where each value sits: range → range = T₁ − T₂ · approach → approach = T₂ − WBT

▶ Try it: Cooling tower: move the temperatures — range, approach and effectiveness
What it means

Range as a share of the ideal range (hot water to wet-bulb); 100 % would mean the water reached the wet-bulb.

Worked example. Range 8, approach 5.5 → 8 ÷ 13.5 = 59 %.
Exam trap. Denominator is range PLUS approach.

Cooling capacity (heat rejected)

= m × Cp × (T₁ − T₂)
Symbols · units
Symbolsm = water flow (kg/hr = m³/hr × 1000), Cp = 1 kcal/kg °C
Answer unitkcal/hr (÷ 3024 = TR)
Book topicPerformance
fillhot water in T₁cold out T₂air in (WBT)evaporation + driftblowdownmake-upm

Where each value sits: m → circulation rate m³/hr, m, Cp · Cp → circulation rate m³/hr, m, Cp

What it means

The heat the tower throws away = water flow × 1 kcal/kg °C × range; divide by 3,024 for TR.

Worked example. 3,000 m³/hr × 1000 × (41 − 31) = 30 million kcal/hr (book) ≈ 9,920 TR. 2 m³/min, 43 → 35 °C: 120,000 kg/hr × 8 ÷ 3,024 = 317 TR (2013 S-5).
Exam trap. m³/hr × 1000 = kg/hr; Cp of water = 1.

Range from heat load

= Heat load (kcal/hr) ÷ Water circulation rate (litres/hr)
Symbols · units
Symbolskcal/hr, LPH
Answer unit°C
Book topicRange
fillhot water in T₁cold out T₂air in (WBT)evaporation + driftblowdownmake-upkcal/hr

Where each value sits: kcal/hr → circulation rate m³/hr, m, Cp · LPH → circulation rate m³/hr, m, Cp

What it means

If you know the heat load and the circulation rate, the range follows — the tower cannot change it.

Worked example. 6,000,000 kcal/hr ÷ 1,000,000 L/hr = 6 °C.
Exam trap. Litres per hour in the denominator (= kg/hr for water).

Evaporation loss

= 0.00085 × 1.8 × Circulation rate (m³/hr) × (T₁ − T₂)
Symbols · units
Symbolsm³/hr, °C
Answer unitm³/hr
Book topicWater losses
fillhot water in T₁cold out T₂air in (WBT)evaporation + driftblowdownmake-upm³/hr

Where each value sits: m³/hr → circulation rate m³/hr, m, Cp · °C: °C

▶ Try it: Cooling tower water: raise the cycles of concentration — blowdown falls
evaporation blowdown make-up
What it means

Cooling happens mainly by evaporating about 1 % of the water for every 5.5–6 °C of range; this water is lost and must be made up.

Worked example. 1,000 m³/hr, range 8: 0.00085 × 1.8 × 1,000 × 8 = 12.2 m³/hr (≈ 1.2 %).
Exam trap. Multiply by BOTH constants 0.00085 and 1.8 (book form).

Cycles of concentration

COC = Dissolved solids in circulating water ÷ Dissolved solids in make-up water
Symbols · units
Symbolsppm (or conductivity)
Answer unitno unit
Book topicWater losses
fillhot water in T₁cold out T₂air in (WBT)evaporation + driftblowdownmake-upTDS circulatingTDS make-upCOC

Where each value sits: TDS circulating → circulation rate m³/hr, m, Cp · TDS make-up → make-up = E + B + D · COC → blowdown B, COC

▶ Try it: Cooling tower water: raise the cycles of concentration — blowdown falls
evaporation blowdown make-up
What it means

Because only pure water evaporates, dissolved solids build up; COC says how many times more concentrated the circulating water is than the make-up. Higher COC = less blowdown = less water, until scaling limits it.

Worked example. Circulating TDS 1,500 ppm, make-up 500 → COC 3.
Exam trap. Also = make-up ÷ blowdown = conductivity ratio.

Blowdown

= Evaporation loss ÷ (COC − 1)
Symbols · units
Symbolsm³/hr
Answer unitm³/hr
Book topicWater losses
fillhot water in T₁cold out T₂air in (WBT)evaporation + driftblowdownmake-upm³/hr

Where each value sits: m³/hr → circulation rate m³/hr, m, Cp

▶ Try it: Cooling tower water: raise the cycles of concentration — blowdown falls
evaporation blowdown make-up
What it means

Water deliberately drained to keep TDS at the chosen COC. Raising COC from 3 to 5 halves blowdown (÷2 vs ÷4).

Worked example. Evaporation 12.2 m³/hr, COC 3 → 12.2 ÷ 2 = 6.1 m³/hr; at COC 5 → 3.05.
Exam trap. Denominator is (COC − 1), not COC — and increasing COC DECREASES blowdown (2009/2018 objective).

Make-up water

= Evaporation + Blowdown + Drift
Symbols · units
Symbolsm³/hr
Answer unitm³/hr
Book topicWater losses
fillhot water in T₁cold out T₂air in (WBT)evaporation + driftblowdownmake-upm³/hr

Where each value sits: m³/hr → circulation rate m³/hr, m, Cp

▶ Try it: Cooling tower water: raise the cycles of concentration — blowdown falls
evaporation blowdown make-up
What it means

Everything lost must be replaced: evaporation + blowdown + drift (windage, ≈ 0.1–0.3 %).

Worked example. 12.2 + 6.1 + 1.0 = 19.3 m³/hr.
Exam trap. Drift is small but the exam expects it in the sum.

Liquid-to-gas (L/G) ratio

L × (T₁ − T₂) = G × (h₂ − h₁) → L/G = (h₂ − h₁) ÷ (T₁ − T₂)
Symbols · units
SymbolsL, G = water, air mass flow (kg/hr); h = air enthalpy at exit / inlet wet bulb
Answer unitkg/kg
Book topicL/G ratio
fillhot water in T₁cold out T₂air in (WBT)evaporation + driftblowdownmake-upLGh

Where each value sits: L → L/G = water ÷ air mass · G → air G, density, enthalpy h₁ h₂ · air → air G, density, enthalpy h₁ h₂ · h → T₁ hot water in

What it means

Mass of water per mass of air through the tower; the heat lost by the water equals the heat gained by the air, so L/G = enthalpy rise of air ÷ temperature drop of water. Typical 0.75–1.5.

Worked example. Air enthalpy in 20, out 30 kcal/kg; water 43 → 35: L/G = 10 ÷ 8 = 1.25.
Exam trap. It is MASS flow of water ÷ MASS flow of air (2015/2018 objective), not volume.

Air mass flow

= Air volume flow × Air density
Symbols · units
Symbolsm³/hr × kg/m³
Answer unitkg/hr
Book topicL/G ratio
fillhot water in T₁cold out T₂air in (WBT)evaporation + driftblowdownmake-upm³/hr

Where each value sits: m³/hr → circulation rate m³/hr, m, Cp

What it means

Fan air volume × air density; needed to compute L/G.

Worked example. 989,544 m³/hr × 1.08 kg/m³ = 1,068,700 kg/hr (book trial).
Exam trap. Density of hot humid air ≈ 1.08, not 1.2.

% evaporation loss

= Evaporation ÷ Circulation rate × 100
Symbols · units
Symbolsm³/hr
Answer unit%
Book topicWater losses
fillhot water in T₁cold out T₂air in (WBT)evaporation + driftblowdownmake-upm³/hr

Where each value sits: m³/hr → circulation rate m³/hr, m, Cp

What it means

Evaporation as a share of circulation — a sanity check (about 1 % per 6 °C of range).

Worked example. 12.2 ÷ 1,000 = 1.2 %.

Range, approach and effectiveness

°C 43 hot water in 35 cold water out 29.5 ambient wet-bulb Range 8 °C (set by process) Approach 5.5 °C (tower performance) Effectiveness = Range ÷ (Range + Approach) = 8 ÷ 13.5 = 59 %. Lower approach = better (and bigger) tower.

Cooling-tower water balance

Cooling towercirculating water 1,000 m³/hr evaporation 12.2 (pure water) blowdown = E ÷ (COC − 1) = 6.1 drift ≈ 1.0 make-up 19.3 = E + B + D Only pure water evaporates, so TDS rises: COC = TDS circulating ÷ TDS make-up. Higher COC → less blowdown.
Definitions the exam asks
Tower types
Natural draft (hyperbolic, power plants) and mechanical draft — forced (fan at inlet) or induced (fan at top, most common in industry); counter-flow vs cross-flow.
Fill
Splash fill (droplets, 30–45 m²/m³) and film fill (thin film over sheets, 150 m²/m³, more efficient but fouls).
Drift eliminator
Captures water droplets carried out in the air stream leaving the tower.
Factors affecting performance
Wet-bulb temperature, range, approach, heat load, L/G ratio, fill condition, water distribution. If heat load, range and WBT are fixed, a smaller approach needs a bigger tower.
Book performance norms
Approach 2.8–5.5 °C typical; % evaporation ≈ 1 % per 6 °C range.
Verified videos for this chapter (YouTube)
Range, Approach & Effectiveness — Range and Approach of Cooling Tower | Cooling Tower Factors: Range & Approach | Wet Bulb Temperature · Core EngineeringWater Balance, Evaporation & Blowdown — Cooling Tower Calculations In Hindi | Cooling Tower Range And Approach | Efficiency Calculation · Sandeep Academy [IITR, GATE AIR 1]L/G Ratio & Fill Media — COOLING TOWER PERFORMANCE || How to check cooling tower performance in 10 minutes || · Power Plant Discussion

Chapter 8 · Lighting System

~7 marks, mostly easy objectives: lux/lumen, efficacy ranking, lamp types, T-numbers, CRI; one lumen-method numerical.

Street-light luminaire (HPSV/LED) — luminaire distributes and controls the lamp's light
Street-light luminaire (HPSV/LED) — luminaire distributes and controls the lamp's lightPhoto: Bidgee · CC BY 3.0 · source
Compact fluorescent lamps
Compact fluorescent lampsPhoto: SecretDisc · CC BY-SA 3.0 · source
Tubular lamps — T-number gives the tube diameter in eighths of an inch
Tubular lamps — T-number gives the tube diameter in eighths of an inchPhoto: Dmitry G · CC BY-SA 3.0 · source

Illuminance – inverse square law

E = I ÷ d²
Symbols · units
SymbolsI = luminous intensity of the source (book writes it in lumens), d = distance (m)
Answer unitlux (lm/m²)
Book topicBasic terms
work plane (0.8–0.9 m above floor)Id

Where each value sits: I → lamp: lumens F, watts, efficacy lm/W · d → mounting height Hm, distance d

▶ Try it: Lighting: move the lamp away — illuminance falls with distance²
What it means

Light spreads out: doubling the distance from a small source quarters the illuminance on the surface.

Worked example. 10 lux at 1 m → 2.5 lux at 2 m.
Exam trap. Divide by distance SQUARED.

Inverse square law – two distances

E₁ × d₁² = E₂ × d₂²
Symbols · units
Symbolslux, m
Answer unitlux
Book topicBasic terms
work plane (0.8–0.9 m above floor)lux

Where each value sits: lux → illuminance E lux, area A · m: m

▶ Try it: Lighting: move the lamp away — illuminance falls with distance²
What it means

Same law rearranged to compare two distances.

Worked example. E₁ = (d₂/d₁)² × E₂ = (1.0/0.5)² × 10 = 40 lux (book).
Exam trap. Square the ratio of distances.

Lux (definition)

1 lux = 1 lumen ÷ 1 m²
Symbols · units
Symbolslumen, m²
Answer unitlm/m²
Book topicBasic terms
work plane (0.8–0.9 m above floor)lumen

Where each value sits: lumen → lamp: lumens F, watts, efficacy lm/W · m²: m²

What it means

One lumen of light spread over one square metre. Offices need ~300–500 lux, corridors ~100, precision work 1,000+.

Worked example. 300 lux on 216 m² needs 64,800 lumens (2025 S-1).
Exam trap. Lux is per m²; lumen is the total light output.

Luminous efficacy

= Luminous flux (lm) ÷ Lamp power (W)
Symbols · units
Symbolslm, W
Answer unitlm/W
Book topicBasic terms
work plane (0.8–0.9 m above floor)lm

Where each value sits: lm → lamp: lumens F, watts, efficacy lm/W · W → lamp: lumens F, watts, efficacy lm/W

What it means

Lumens of light per watt of electricity — the efficiency of a lamp. Ranking: LPSV > HPSV ≈ LED > metal halide > CFL > FTL > HPMV > halogen > incandescent.

Worked example. 18 W LED tube giving 1,800 lm → 100 lm/W.
Exam trap. Efficacy is a property of the LAMP; circuit efficacy includes the ballast/driver.

Maximum possible luminous efficacy

1 W = 683 lm at 555 nm
Symbols · units
Symbols—
Answer unitlm/W
Book topicBasic terms
work plane (0.8–0.9 m above floor)683 lm/W

Where each value sits: 683 lm/W → lamp: lumens F, watts, efficacy lm/W · 555 nm → lamp: lumens F, watts, efficacy lm/W

What it means

If every watt became visible green light at 555 nm (the eye's peak sensitivity) you would get 683 lm — the physical ceiling.

Worked example. A 100 lm/W lamp is 15 % of the maximum.
Exam trap. 683 lm/W at 555 nm, not white light.

Installed load efficacy (ILE)

= Average maintained illuminance (lux) ÷ Installed power density (W/m²)
Symbols · units
Symbolslux, W/m²
Answer unitlux/W/m²
Book topicBasic terms
work plane (0.8–0.9 m above floor)luxW/m²

Where each value sits: lux → illuminance E lux, area A · W/m² → lamp: lumens F, watts, efficacy lm/W

What it means

How much illuminance you get per watt per square metre — judges the whole installation (lamps + luminaires + layout), not just the lamp.

Worked example. 300 lux at 12 W/m² → 25 lux per W/m².
Exam trap. Higher ILE = better installation.

Installed power density (lighting power density)

= Total lighting load (W) ÷ Floor area (m²)
Symbols · units
SymbolsW, m²
Answer unitW/m² (book: per 100 lux)
Book topicBasic terms
work plane (0.8–0.9 m above floor)W

Where each value sits: W → lamp: lumens F, watts, efficacy lm/W · m²: m²

What it means

Watts of lighting per square metre of floor; ECBC limits it (e.g. offices ≈ 10.8 W/m², Ch10).

Worked example. 2.1 kW over 200 m² = 10.5 W/m².
Exam trap. The book also quotes it 'per 100 lux' for comparison between spaces.

Room index

RI = (L × W) ÷ [Hm × (L + W)]
Symbols · units
SymbolsL, W = room length, width (m), Hm = mounting height (m)
Answer unitno unit
Book topicLighting design
work plane (0.8–0.9 m above floor)LWHm

Where each value sits: L → room L × W, room index, UF, LLF · W → lamp: lumens F, watts, efficacy lm/W · width → lamp: lumens F, watts, efficacy lm/W · Hm → mounting height Hm, distance d

What it means

A shape factor: big low rooms have a high index (light reaches the work plane easily); tall narrow rooms a low one. It is looked up against the luminaire's utilisation factor table.

Worked example. 10 × 10 m room, mounting height 2.0 m → 100 ÷ (2 × 20) = 2.5 (book).
Exam trap. Mounting height is luminaire height ABOVE THE WORK PLANE, not above the floor.

Mounting height

Hm = Luminaire height − Work-plane height
Symbols · units
Symbolsm
Answer unitm
Book topicLighting design
work plane (0.8–0.9 m above floor)luminaire htwork-plane htHm

Where each value sits: luminaire ht → lamp: lumens F, watts, efficacy lm/W · work-plane ht → illuminance E lux, area A · Hm → mounting height Hm, distance d

What it means

Distance from the luminaire down to the work plane (desk height ≈ 0.8–0.9 m).

Worked example. Luminaire at 2.9 m, work plane 0.9 m → 2.0 m (book).
Exam trap. Subtract the work-plane height.

Light loss factor

LLF = Lamp lumen MF × Luminaire MF × Room surface MF
Symbols · units
SymbolsMF = maintenance factor (no unit)
Answer unitno unit
Book topicLighting design
work plane (0.8–0.9 m above floor)MF

Where each value sits: MF → room L × W, room index, UF, LLF

What it means

Lamps dim with age, luminaires and room surfaces get dirty; LLF (≈ 0.7–0.8) allows for this so the design still meets the lux at maintenance time.

Worked example. 0.9 × 0.9 × 0.9 = 0.73.
Exam trap. Multiply the three maintenance factors.

Number of fittings required

N = (E × A) ÷ (F × UF × LLF)
Symbols · units
SymbolsE = required lux, A = area (m²), F = lumens per fitting, UF = utilisation factor
Answer unitnumber
Book topicLighting design
work plane (0.8–0.9 m above floor)EFUF

Where each value sits: E → illuminance E lux, area A · A → illuminance E lux, area A · F → lamp: lumens F, watts, efficacy lm/W · UF → room L × W, room index, UF, LLF

What it means

The lumen method: total lumens needed ÷ lumens each fitting actually delivers to the work plane.

Worked example. 216 m² at 300 lux, 18 W LED tubes of 1,800 lm, UF 0.5, LLF 0.8: N = 64,800 ÷ (1,800 × 0.5 × 0.8) = 90 tubes (2025 S-1 pattern).
Exam trap. F is lumens per FITTING (twin-tube = 2 lamps); round UP.

Space-to-height ratio

SHR = Spacing between luminaires ÷ Mounting height
Symbols · units
Symbolsm ÷ m
Answer unitno unit
Book topicLighting design
work plane (0.8–0.9 m above floor)spacingHm

Where each value sits: spacing → spacing, SHR · Hm → mounting height Hm, distance d

What it means

Spacing between luminaires divided by mounting height; keep at or below the luminaire's recommended value (≈ 1.5) for uniform light.

Worked example. Spacing 3 m, height 2 m → 1.5.
Exam trap. Exceeding it gives dark patches between fittings.

Uniformity ratio

= Minimum illuminance ÷ Average illuminance
Symbols · units
Symbolslux
Answer unitno unit
Book topicLighting design
work plane (0.8–0.9 m above floor)lux

Where each value sits: lux → illuminance E lux, area A

What it means

Minimum lux ÷ average lux on the work plane; aim ≥ 0.7.

Worked example. Min 210, average 300 → 0.7.

Inverse-square law

lamp I d = 1 m → E = I/1² d = 2 m → E = I/4 (spread over 4× area)

Lumen method of lighting design

room 18 × 12 m = 216 m², target 300 lux → 64,800 lm needed N = E × A ÷ (F × UF × LLF) F = lumens per fitting · UF = utilisation factor (from room index) · LLF = light loss factor (≈ 0.8) Room index = L × W ÷ [Hm × (L + W)], Hm = luminaire height above the work plane Efficacy (lm/W) ranking: LPSV > HPSV ≈ LED > metal halide > CFL > FTL > HPMV > halogen > incandescent
Definitions the exam asks
Lamp families
Incandescent (efficacy 10–15 lm/W, CRI 100), halogen, FTL (T12 38 mm, T8 26 mm, T5 16 mm), CFL, HPMV, metal halide, HPSV (~120 lm/W, CRI 20–30), LPSV (highest efficacy ~180 lm/W, CRI 10, monochromatic), LED.
Colour rendering index
How true colours look under the lamp, 0–100; incandescent/halogen = 100 (best for colour-critical work), LPSV = 10.
Ballasts
Electromagnetic ballasts lose 10–15 W per tube; electronic ballasts save 20–30 %, run at high frequency, no flicker.
Controls
Occupancy sensors (infrared, ultrasonic, microwave), daylight-linked dimming, timers, task lighting.
Verified videos for this chapter (YouTube)
Lux, Inverse Square Law & Efficacy — Lighting Calculations, Inverse Square, Cosine, Efficacy & Lumen Method for Design Explained · Sparky HelpLamp Efficacy Hierarchy & T-Diameters — Understanding LED Light Fixture Efficacy: How to Calculate Efficiency and Choose the Right Fixture · ShainARTLumen Method & Room Index Design — How Much Light Does My Room Need? Lighting Design | Lighting Calculation Formula · Surviving Architecture

Chapter 9 · DG Set System

~11 marks: SFC and efficiency numericals, loss split (exhaust largest), waste-heat recovery, sizing with diversity factor.

Packaged diesel generator set in an acoustic enclosure
Packaged diesel generator set in an acoustic enclosurePhoto: Gregsedits · CC BY-SA 3.0 · source
Diesel engine coupled to its alternator
Diesel engine coupled to its alternatorPhoto: Wikimedia Commons · CC BY-SA 3.0 · source

Real power of a DG set

kW = kVA × PF
Symbols · units
SymbolskVA, PF
Answer unitkW
Book topicDG basics
diesel enginealternatorloadexhaust ~30 %jacket water ~25 %kVAPF

Where each value sits: kVA → kVA rating, BHP × 0.746 · PF → kW = kVA × PF, units generated

▶ Try it: DG set: load, PF and specific fuel consumption → litres per hour and efficiency
alternator fuel
What it means

A genset is rated in kVA at 0.8 PF; the kW it can deliver is the kVA times the power factor of the load.

Worked example. 1,000 kVA at 0.8 → 800 kW.
Exam trap. Higher-PF loads let you use more of the kVA as kW, but the ENGINE kW limits it.

Apparent power, 3-phase

kVA = √3 × V × I ÷ 1000
Symbols · units
SymbolsV (V), I (A)
Answer unitkVA
Book topicDG basics
diesel enginealternatorloadexhaust ~30 %jacket water ~25 %V

Where each value sits: V → kVA rating, BHP × 0.746 · I → kVA rating, BHP × 0.746

What it means

Alternator output from measured line volts and amps.

Worked example. 420 V, 100 A → 72.7 kVA; at PF 0.9 → 65.5 kW (2009/2022).
Exam trap. Line voltage × √3.

Engine power from BHP

kW = BHP × 0.746
Symbols · units
SymbolsBHP
Answer unitkW
Book topicDG basics
diesel enginealternatorloadexhaust ~30 %jacket water ~25 %BHP

Where each value sits: BHP → kVA rating, BHP × 0.746

What it means

Engines are rated in brake horsepower; multiply by 0.746 for kW.

Worked example. 250 BHP → 186.5 kW.
Exam trap. 1 HP = 0.746 kW (not 0.735).

Fuel consumption

Fuel (litres/hr) = kW generated × SFC (litres/kWh)
Symbols · units
SymbolskW, litres/kWh
Answer unitlitres/hr
Book topicPerformance
diesel enginealternatorloadexhaust ~30 %jacket water ~25 %kWlitres/kWh

Where each value sits: kW → kW = kVA × PF, units generated · litres/kWh → fuel L/h, SFC, GCV, density

▶ Try it: DG set: load, PF and specific fuel consumption → litres per hour and efficiency
alternator fuel
What it means

Litres of diesel per hour = kW generated × litres per kWh (the SFC). A DG set at a lower PF generates fewer kW for the same kVA, so burns less fuel.

Worked example. 65.5 kW × 0.3 L/kWh = 19.64 L/h (2009/2022 objective). 70 L/h ÷ 0.33 L/kWh = 212 kW → ÷ 0.8 = 265 kVA (2021).
Exam trap. SFC in litres per kWh in this form; specific generation (kWh/L) is its inverse.

Specific energy generation

= kWh generated ÷ Litres of fuel used
Symbols · units
SymbolskWh, litres
Answer unitkWh/litre
Book topicPerformance
diesel enginealternatorloadexhaust ~30 %jacket water ~25 %kWhlitres

Where each value sits: kWh → kW = kVA × PF, units generated · litres → fuel L/h, SFC, GCV, density

What it means

Units per litre of diesel — the everyday DG benchmark (3–4 kWh/L for a healthy set; falls at low load).

Worked example. 1,500 kWh in a 2-h trial burning 400 L → 3.75 kWh/L.
Exam trap. Inverse of SFC.

DG overall efficiency

η = (kWh × 860) ÷ (Fuel litres × Density × GCV) × 100
Symbols · units
Symbols1 kWh = 860 kcal; density (kg/litre); GCV (kcal/kg)
Answer unit%
Book topicPerformance
diesel enginealternatorloadexhaust ~30 %jacket water ~25 %1 kWhdensity

Where each value sits: 1 kWh → kW = kVA × PF, units generated · density → fuel L/h, SFC, GCV, density · GCV → fuel L/h, SFC, GCV, density

▶ Try it: DG set: load, PF and specific fuel consumption → litres per hour and efficiency
alternator fuel
What it means

Electrical energy out ÷ fuel energy in: units × 860 kcal, over litres × density (0.85 kg/L) × GCV.

Worked example. 3.5 kWh/L: 3.5 × 860 ÷ (0.85 × 10,200) = 34.7 % (2013 exam; 2025 L-5 gives 34.2 %).
Exam trap. Convert litres to kg with the density before applying GCV.

Waste heat recoverable from exhaust

= kWh/hr × 8 kg gas/kWh × 0.25 kcal/kg °C × (T exhaust − T out)
Symbols · units
Symbolstemperatures (°C)
Answer unitkcal/hr
Book topicWaste heat recovery
diesel enginealternatorloadexhaust ~30 %jacket water ~25 %kWh/hr8 kg/kWh

Where each value sits: kWh/hr → kW = kVA × PF, units generated · 8 kg/kWh → exhaust: 8 kg/kWh, Cp 0.25, T in/out · 0.25 → exhaust: 8 kg/kWh, Cp 0.25, T in/out · T exhaust − T out → exhaust: 8 kg/kWh, Cp 0.25, T in/out

What it means

Exhaust gas (≈ 8 kg per kWh at ≈ 450 °C) can heat water or make steam down to about 180 °C; the recoverable heat is mass × Cp × temperature drop.

Worked example. 600 kWh/h × 8 × 0.25 × (450 − 230) = 264,000 kcal/hr (book).
Exam trap. Cp of exhaust gas 0.25 kcal/kg °C, and do not cool below the stated outlet temperature.

Steam generated from waste heat

= Waste heat (kcal/hr) ÷ (Steam enthalpy − Feed-water enthalpy)
Symbols · units
Symbolsenthalpy (kcal/kg)
Answer unitkg/hr
Book topicWaste heat recovery
diesel enginealternatorloadexhaust ~30 %jacket water ~25 %enthalpy

Where each value sits: enthalpy → steam kg/hr, enthalpy

What it means

Recoverable heat divided by the heat needed per kg of steam (steam enthalpy minus feed-water enthalpy).

Worked example. 264,000 ÷ (650.57 − 80) = 462.7 kg/h (book).
Exam trap. Feed-water enthalpy ≈ its temperature in °C (kcal/kg).

Heat lost to jacket cooling water

Q = m × Cp × ΔT ; kW = Q ÷ 860
Symbols · units
Symbolsm (kg/hr), Cp = 1 kcal/kg °C, ΔT (°C)
Answer unitkcal/hr (and kW)
Book topicHeat balance
diesel enginealternatorloadexhaust ~30 %jacket water ~25 %m

Where each value sits: m → m, Cp, ΔT jacket water · Cp → m, Cp, ΔT jacket water · ΔT → m, Cp, ΔT jacket water

What it means

Engine cooling water carries away ~25–30 % of fuel energy; from its flow and temperature rise.

Worked example. 12.9 m³/hr × 1000 × 1 × 10 °C = 129,000 kcal/hr ÷ 860 = 150 kW (book / 2014).
Exam trap. Divide by 860 to get kW.

Maximum demand from connected load

= Connected load × Diversity factor
Symbols · units
SymbolskW; diversity factor as fraction
Answer unitkW
Book topicSizing
diesel enginealternatorloadexhaust ~30 %jacket water ~25 %kWdiversity

Where each value sits: kW → kW = kVA × PF, units generated · diversity → connected load, diversity, load factor, %

What it means

Not all loads run at once; the diversity factor gives the realistic peak the DG must carry.

Worked example. 650 kW connected × 0.54 = 351 kW (book). When the factor is quoted as a number > 1, DIVIDE: 650 ÷ 1.8.
Exam trap. Read whether the diversity factor is a fraction (< 1, multiply) or a ratio (> 1, divide).

DG set rating

= kVA required ÷ Load factor
Symbols · units
SymbolskVA; load factor as fraction
Answer unitkVA
Book topicSizing
diesel enginealternatorloadexhaust ~30 %jacket water ~25 %kVAload

Where each value sits: kVA → kVA rating, BHP × 0.746 · load → connected load, diversity, load factor, %

What it means

Size the set so the peak demand is a comfortable load (70–80 %) — running lightly loaded wastes fuel and causes glazing.

Worked example. 351 kW ÷ 0.8 PF = 439 kVA ÷ 0.8 load factor → 550 kVA.
Exam trap. kW → kVA (÷ PF) BEFORE applying the load factor.

Load factor

= Average load ÷ Maximum (rated) load
Symbols · units
SymbolskW or kVA
Answer unit% (or fraction)
Book topicSizing
diesel enginealternatorloadexhaust ~30 %jacket water ~25 %kW

Where each value sits: kW → kW = kVA × PF, units generated

What it means

Average load ÷ peak load over the period; a low load factor means a big set idling most of the time.

Worked example. Average 300 kW, peak 500 → 60 %.

Cost of generation

= Fuel cost per hour (Rs/hr) ÷ kWh generated per hour
Symbols · units
SymbolsRs/hr, kWh/hr
Answer unitRs/kWh
Book topicEconomics
diesel enginealternatorloadexhaust ~30 %jacket water ~25 %Rs/hrkWh/hr

Where each value sits: Rs/hr → ₹/L, ₹/kWh · kWh/hr → kW = kVA × PF, units generated

What it means

Fuel cost per unit generated; compare with the grid tariff to decide when to run the set.

Worked example. 19.6 L/h × ₹90 ÷ 65.5 kWh = ₹27/kWh.
Exam trap. Add lubricant and maintenance for the full cost.

Sankey diagram of a diesel generator

Diesel 100 % Electricity ≈ 35 % Exhaust gas ≈ 30 % (largest loss → WHR) Jacket cooling water ≈ 25 % Radiation & others ≈ 10 %
Definitions the exam asks
DG basics
4-stroke diesel engine + alternator at 1,500 rpm (4-pole, 50 Hz); rated kVA at 0.8 PF; efficiency ≈ 35 %.
Losses
Exhaust gas ≈ 30 % (largest), jacket water ≈ 25 %, radiation ≈ 10 % — recover exhaust heat for steam/hot water, jacket water for absorption chillers.
Loading
Run at 70–80 % load; light loading wastes fuel and glazes cylinders. Max PF usable = (engine kW − losses) ÷ kVA.
Derating
Output falls with altitude and ambient temperature (book Tables 9.3/9.4).
Parameters to monitor
Voltage and frequency (plus current and PF) on the generator panel.
Verified videos for this chapter (YouTube)
4-Stroke Principles & Sizing — Energy Efficiency in Diesel Generator (DG) Sets · bhavesh swamiHeat Balance & Exhaust WHR — Diesel Generatior Fuel consumption caluclation theortically practically in electrical explanations · Electrical Explanations

Chapter 10 · Buildings and ECBC

~15 marks: ECBC applicability, envelope terms (WWR, EA, SHGC, U-factor), EPI/star rating, LPD — the 2025 long question was a full EPI/LPD/diversity calculation.

Office façade — window-wall ratio, SHGC and VLT of the glazing decide the cooling load and daylight
Office façade — window-wall ratio, SHGC and VLT of the glazing decide the cooling load and daylightPhoto: Calderoliver · CC BY-SA 3.0 · source
Building envelope: glazing and shading
Building envelope: glazing and shadingPhoto: Jon Rawlinson · CC BY 2.0 · source

Energy Performance Index

EPI = Annual energy consumption ÷ Built-up area
Symbols · units
SymbolskWh/year, m²
Answer unitkWh/m²/year
Book topicStar rating of buildings
roof (reflectance, emittance, U-factor)solar radiation W/m²lighting, appliances, HVAC, UPSkWh/year

Where each value sits: kWh/year → annual kWh, built-up area m² → EPI · m²: m²

▶ Try it: Building: annual energy and built-up area → EPI and star rating
EPI scale for offices (book bands, composite climate): ≤ 90 → 5★ … ≥ 190 → 1★
What it means

The building's annual energy per square metre of built-up area — the number used for BEE star rating of offices (lower EPI = MORE stars).

Worked example. 107,889 kWh ÷ 3,592 m² = 30 kWh/m²/yr → 5-star (2025 L-5). Bands for offices ≈ 190 (1★) down to 90 (5★) in the book's climate table.
Exam trap. Built-up area, not carpet area; and LOWER EPI is BETTER (2013/2018 objective).

AAhEPI (BPO star rating)

= EPI × 1000 ÷ Annual operating hours (hours/day × days/week × 52)
Symbols · units
SymbolsEPI (kWh/m²/yr), hours
Answer unit(Wh/m²)/hr
Book topicStar rating of buildings
roof (reflectance, emittance, U-factor)solar radiation W/m²lighting, appliances, HVAC, UPSEPIhours

Where each value sits: EPI → reflectance + absorptance = 1, emissivity e · hours → hours/day × days/week × 52 → AAhEPI

What it means

BPOs run round the clock, so their EPI is normalised by operating hours: watt-hours per m² per operating hour.

Worked example. EPI 250 kWh/m²/yr, 24 h × 7 d × 52 = 8,736 h → 250 × 1000 ÷ 8,736 = 28.6 (Wh/m²)/hr.
Exam trap. Unit is (Wh/sqm)/hr (book Q9).

Window-wall ratio

WWR = Vertical fenestration area ÷ Gross exterior wall area
Symbols · units
Symbolsm², m²
Answer unitno unit (or %)
Book topicBuilding envelope
roof (reflectance, emittance, U-factor)solar radiation W/m²lighting, appliances, HVAC, UPSfenestration aregross wall area

Where each value sits: fenestration area → fenestration area, WWR, VLT, SHGC, U · gross wall area → gross exterior wall area · WWR → fenestration area, WWR, VLT, SHGC, U

What it means

How much of the outside wall is glass; more glass = more daylight but more solar heat gain.

Worked example. 60 m² window in 150 m² wall → 0.40.
Exam trap. Gross exterior wall area in the denominator (2022 objective).

Effective aperture

EA = VLT × WWR
Symbols · units
Symbolsno units
Answer unitno unit (complies if EA ≥ 0.1)
Book topicBuilding envelope
roof (reflectance, emittance, U-factor)solar radiation W/m²lighting, appliances, HVAC, UPSVLT

Where each value sits: VLT → fenestration area, WWR, VLT, SHGC, U · WWR → fenestration area, WWR, VLT, SHGC, U · EA ≥ 0.1 → fenestration area, WWR, VLT, SHGC, U

What it means

Daylight potential = how much wall is glass × how much light the glass passes; ECBC wants EA ≥ 0.1 so daylight can replace lighting.

Worked example. WWR 0.4 × VLT 0.26 = 0.104 → complies; 0.6 × 0.15 = 0.09 → does not (book cases, 2023 S-3).
Exam trap. Both factors are fractions; compare with 0.1.

Visible light transmittance

VLT = Light through glazing ÷ Light through perfectly transmissive glazing
Symbols · units
Symbols—
Answer unitno unit (0 to 1)
Book topicBuilding envelope
roof (reflectance, emittance, U-factor)solar radiation W/m²lighting, appliances, HVAC, UPSlight through gl

Where each value sits: light through glazing → fenestration area, WWR, VLT, SHGC, U · VLT → fenestration area, WWR, VLT, SHGC, U

What it means

Share of visible light the glazing lets through (clear glass ≈ 0.8, tinted 0.2–0.5).

Worked example. VLT 0.5 passes half the daylight.
Exam trap. Not the same as SHGC — VLT is light, SHGC is heat.

Solar heat gain coefficient

SHGC = Solar heat gain through fenestration ÷ Incident solar radiation
Symbols · units
Symbols—
Answer unitno unit (0 to 1)
Book topicBuilding envelope
roof (reflectance, emittance, U-factor)solar radiation W/m²lighting, appliances, HVAC, UPSsolar gain throuincident radiati

Where each value sits: solar gain through glass → fenestration area, WWR, VLT, SHGC, U · incident radiation → incident solar radiation, gain W/m² · SHGC → fenestration area, WWR, VLT, SHGC, U

What it means

Share of the sun's heat that gets through the window (directly plus re-radiated). SHGC 0.30 means 30 % of incident solar heat enters; the rest is reflected or re-emitted outside.

Worked example. SHGC 0.30 → 'the window allows 30 % of the sun's heat into the interior' (2018/2021/2022 objective).
Exam trap. Lower SHGC = less cooling load; it is NOT '70 % reflected' (some is absorbed and re-emitted).

Solar heat gain through glass

= SHGC × Incident solar radiation
Symbols · units
SymbolsW/m²
Answer unitW/m²
Book topicBuilding envelope
roof (reflectance, emittance, U-factor)solar radiation W/m²lighting, appliances, HVAC, UPSW/m²

Where each value sits: W/m² → incident solar radiation, gain W/m²

What it means

Incident solar radiation times the SHGC.

Worked example. 600 W/m² × 0.25 = 150 W/m² (2024 L-3); 700 × 0.30 = 210 W/m².
Exam trap. Per m² of glass; multiply by the glass area for total watts.

Heat flow through a wall or window

Q = U × A × ΔT
Symbols · units
SymbolsU = U-factor (W/m² °C), A = area (m²), ΔT (°C)
Answer unitW
Book topicU-factor
roof (reflectance, emittance, U-factor)solar radiation W/m²lighting, appliances, HVAC, UPSU

Where each value sits: U → fenestration area, WWR, VLT, SHGC, U · A → fenestration area, WWR, VLT, SHGC, U · ΔT → fenestration area, WWR, VLT, SHGC, U

What it means

The U-factor is the heat that passes through 1 m² for each degree of temperature difference; lower U = better insulation. ECBC max for vertical fenestration ≈ 3.3 W/m²·°C (most zones).

Worked example. U 3.3, 20 m², ΔT 10 °C → 660 W.
Exam trap. U-factor in W/m²·°C; R-value is its inverse.

Reflectance and absorptance (opaque surface)

Reflectance + Absorptance = 1
Symbols · units
Symbols—
Answer unitno unit
Book topicCool roofs
roof (reflectance, emittance, U-factor)solar radiation W/m²lighting, appliances, HVAC, UPSreflectance

Where each value sits: reflectance → reflectance + absorptance = 1, emissivity e · absorptance → reflectance + absorptance = 1, emissivity e

What it means

Whatever sunlight a roof does not reflect, it absorbs; a cool roof has high reflectance (≥ 0.7) AND high emittance (≥ 0.75) so it also radiates the heat away at night.

Worked example. Reflectance 0.7 → absorptance 0.3.
Exam trap. A cool roof REFLECTS heat (book EOC Q5).

Emissivity (thermal emittance)

e = Energy radiated by the material ÷ Energy radiated by a black body at same temperature
Symbols · units
Symbols—
Answer unitno unit (black body = 1)
Book topicCool roofs
roof (reflectance, emittance, U-factor)solar radiation W/m²lighting, appliances, HVAC, UPSeblack body

Where each value sits: e → reflectance + absorptance = 1, emissivity e · black body → incident solar radiation, gain W/m²

What it means

How well a surface radiates heat compared with a perfect black body (e = 1); cool roofs need high emittance.

Worked example. e 0.9 radiates 90 % of the black-body rate.
Exam trap. Dimensionless, 0–1.

Interior lighting power allowance (building area method)

= Gross lighted floor area × Allowed LPD
Symbols · units
Symbolsm² × W/m²
Answer unitW
Book topicECBC lighting
roof (reflectance, emittance, U-factor)solar radiation W/m²lighting, appliances, HVAC, UPSfloor areaallowed LPD

Where each value sits: floor area → annual kWh, built-up area m² → EPI · allowed LPD → lighting W, LPD W/m², floor area · W → lighting W, LPD W/m², floor area

What it means

ECBC cap on total lighting watts for a building type = floor area × allowed LPD.

Worked example. Hotel 4 × 1,000 m² at 10.8 W/m² → 43,200 W (book; 2011/2015/2021/2023/2024 objective).
Exam trap. Use the whole lighted floor area (all floors).

Lighting power density

LPD = Lighting power (W) ÷ Area (m²)
Symbols · units
SymbolsW, m²
Answer unitW/m²
Book topicECBC lighting
roof (reflectance, emittance, U-factor)solar radiation W/m²lighting, appliances, HVAC, UPSlighting Wfloor area m²

Where each value sits: lighting W → lighting W, LPD W/m², floor area · floor area m² → annual kWh, built-up area m² → EPI · LPD → lighting W, LPD W/m², floor area

What it means

Watts per square metre — compare the actual installed lighting with the ECBC allowance.

Worked example. 8.11 kW ÷ 3,592 m² = 2.25 W/m² (2025 L-5).
Exam trap. kW × 1000 before dividing.

UPS efficiency

η = Output power ÷ Input power × 100
Symbols · units
SymbolskW
Answer unit%
Book topicUPS
roof (reflectance, emittance, U-factor)solar radiation W/m²lighting, appliances, HVAC, UPSoutput kWheat loss

Where each value sits: output kW → UPS in / out kW · input kW → UPS in / out kW · heat loss → lighting W, LPD W/m², floor area

What it means

Output ÷ input; losses become heat that the AC must then remove — double penalty.

Worked example. 100 kW in, 90 kW out → 90 %; 10 kW of heat to the room.
Exam trap. In a UPS the inverter converts DC → AC (book EOC Q10).

Building envelope terms

gross wall 300 × 150; windows 2 × (90 × 70) WWR = window ÷ wall = 0.28EA = VLT × WWR (≥ 0.1 complies) SHGC × incident W/m² = heat gainU-factor W/m²·°C: lower = betterEPI = kWh/yr ÷ built-up m² ECBC applies at ≥ 100 kW connected load or ≥ 120 kVA contract demand.
Definitions the exam asks
ECBC
Energy Conservation Building Code (2007) for commercial buildings ≥ 100 kW / 120 kVA: envelope, HVAC, lighting, service hot water, electrical power; five climate zones — hot-dry, warm-humid, composite, moderate, cold (NOT 'cold-humid').
Compliance routes
Prescriptive (meet each limit), envelope trade-off (EPF — envelope performance factor), whole-building performance (simulation of the entire building).
Fenestration
Windows, skylights (slope < 60° from horizontal), glass doors, ventilators — not valves.
Star rating of buildings
BEE rates offices, BPOs, hotels, hospitals by EPI bands per climate zone; lower EPI → more stars.
BEMS / BMS
Building management system: central control of HVAC, lighting, pumps, with monitoring and scheduling.
Verified videos for this chapter (YouTube)
ECBC Scope, Climate Zones & EPI — Energy Conservation Building Code (ECBC) | Class 113 | Anish Kumar Singh| Lukmaan IAS · Lukmaan IASBuilding Envelope: SHGC, WWR & Cool Roofs — ECBC- Energy Conservation Builiding Code | Corporate Film | Raasta Studios · Raasta StudiosCompliance: Prescriptive, Trade-Off & WBP — EnCon_Session-57: Introduction to Energy Conservation Building Code I Building Envelop I Sealing · LogicLoom 4.0
💬 Found a mistake or want something added? Send a message