Energy Efficiency in Electrical Utilities — all 10 chapters, all 137 formulas (the same list as the Formula & Unit Workbook, so nothing is missing). For every formula: what each symbol means and its unit, what the formula tells you, a worked example from a real exam question, and the exam trap. Plus 26 photographs of the actual equipment, 16 diagrams, 20 constants, 48 definitions and 23 verified online videos. Values are the 2014 BEE Book-3's. ▶ Download the whole guide as one PDF · Numericals drill
Constants to memorise (used all through the paper)
1 TR (Ton of Refrigeration) in kcal/hr
3024 kcal/hr
1 TR in kW
3.51 kW
1 TR in BTU/hr
12,000 BTU/hr
1 kW in kcal/hr
860 kcal/hr
1 kWh in kcal
860 kcal
1 BHP in kW
0.746 kW
Acceleration due to gravity, g
9.81 m/s²
Density and specific heat of water
1000 kg/m³ ; Cp = 1 kcal/kg °C
1 kg/cm² pressure as water head
10 m of water column
1 m³/min in cfm
35.31 cfm
Density of air at 0 °C (fans)
1.293 kg/m³
Molecular weight of air
28.92 kg/kg-mole
Maximum luminous efficacy
683 lm/W at 555 nm
Condenser water flow per TR
0.91 m³/hr per TR (4 gpm/TR)
Evaporation per 10,00,000 kcal heat rejected (cooling tower)
1.8 m³
DG exhaust gas: mass per kWh and Cp
8 kg/kWh ; 0.25 kcal/kg °C
Stray load loss of a motor (IS/IEC)
0.5 % of input power
Why 102 in fan efficiency formula
1000 ÷ 9.81 (converts m³/s × mmWC into kW)
Temperature in Kelvin
K = °C + 273
ECBC applies to buildings with
connected load ≥ 100 kW or contract demand ≥ 120 kVA
Chapter 1 · Electrical Systems
~23 marks (15 %) — the top chapter with HVAC. PF/kVAr, transformer losses at part load, maximum demand and AT&C losses come every year as numericals.
Distribution transformer — iron loss is constant, copper loss rises with load²Photo: Cjp24 · CC BY-SA 4.0 · sourcePower-factor correction panel: capacitor banks switched in steps by an automatic PF controllerPhoto: Beuhri at Dutch Wikipedia · Public domain · sourceThree-phase energy meter — records kWh, and kVA maximum demand over 30-minute windowsPhoto: Gpkp · CC BY-SA 4.0 · source
Power factor
PF = cos φ = kW ÷ kVA
Symbols · units
Symbols
kW = real power, kVA = apparent power
Answer unit
no unit (0 to 1)
Book topic
Power factor
Where each value sits: kW → kVA, kVAr, kW · kVA → kVA, kVAr, kW
▶ Try it: Power factor: add capacitor kVAr — watch the triangle shrink
What it means
The fraction of the current that does real work. PF = 1 means every ampere is useful; PF 0.7 means the cables and transformer carry 43 % more current than the work needs.
Worked example. kW 812, kVA 1,160 → PF = 0.70.
Exam trap. PF is a ratio, never a percentage of energy saved.
Apparent power, 3-phase
kVA = √3 × V × I ÷ 1000
Symbols · units
Symbols
V = line voltage (V), I = line current (A)
Answer unit
kVA
Book topic
Power triangle
Where each value sits: V → receiving-end Er, V · I → copper / load loss ∝ load²
What it means
What the supply actually has to deliver — the voltage times the current, before asking how much of it does work. Cables, switchgear and transformers are rated in kVA for this reason.
Worked example. 415 V, 100 A → √3 × 415 × 100 ÷ 1000 = 71.9 kVA.
Exam trap. Use the line-to-line voltage (415 V), not 230 V, for 3-phase.
Real power, 3-phase
kW = √3 × V × I × PF ÷ 1000
Symbols · units
Symbols
V (V), I (A), PF (no unit)
Answer unit
kW
Book topic
Power triangle
Where each value sits: V → receiving-end Er, V · I → copper / load loss ∝ load² · PF → kVAr, φ₁, φ₂, PF
What it means
The power that turns into heat, motion or light — what the kWh meter records. It is the apparent power times the power factor.
Worked example. 415 V, 100 A, PF 0.8 → 57.5 kW.
Exam trap. If PF is not given, do not assume 1 — the question usually gives it.
Relation between kW, kVAr and kVA
kVA² = kW² + kVAr²
Symbols · units
Symbols
kW, kVAr, kVA
Answer unit
kVA
Book topic
Power triangle
Where each value sits: kW → kVA, kVAr, kW · kVAr → kVA, kVAr, kW · kVA → kVA, kVAr, kW
▶ Try it: Power factor: add capacitor kVAr — watch the triangle shrink
What it means
Pythagoras on the power triangle: kW along the base, kVAr up the side, kVA on the diagonal. Given any two you can find the third.
Worked example. kW 812, kVAr 828 → kVA = √(812² + 828²) = 1,160.
Exam trap. kVA is NOT kW + kVAr — they add as a triangle, not in a straight line.
Where each value sits: kW → % load, kVA, kW · φ₁ → kVAr, φ₁, φ₂, PF · φ₂ → kVAr, φ₁, φ₂, PF
▶ Try it: Power factor: add capacitor kVAr — watch the triangle shrink
What it means
How many kVAr of capacitors to add so the existing kW load reaches the target PF. Convert each PF to its angle (φ = cos⁻¹ PF), take the tangents, multiply the difference by the kW.
Worked example. 627 kW from PF 0.72 (tan 0.964) to 0.95 (tan 0.329): 627 × 0.635 = 398 kVAr (the book's example). Useful tangents: 0.7→1.02, 0.8→0.75, 0.85→0.62, 0.9→0.48, 0.95→0.33, 1→0.
Exam trap. Multiply the OPERATING kW (average load), not the kVA and not the nameplate. A capacitor's kVAr output falls with the square of the voltage: at 400 V a 415 V unit gives (400/415)² = 93 %.
Line (copper) loss
P = I² × R
Symbols · units
Symbols
I = current (A), R = resistance (Ω)
Answer unit
W
Book topic
Distribution losses
Where each value sits: I → copper / load loss ∝ load² · R → copper / load loss ∝ load²
What it means
Heat wasted in a conductor. Because it depends on the SQUARE of the current, halving the current (by raising voltage or improving PF) cuts the loss to a quarter.
Worked example. 100 A through 0.1 Ω → 1,000 W; at 50 A → 250 W.
Exam trap. Loss ∝ I², not ∝ I.
% reduction in distribution loss when tail-end PF is raised
[1 − (PF₁ ÷ PF₂)²] × 100
Symbols · units
Symbols
PF₁ = existing PF, PF₂ = improved PF
Answer unit
%
Book topic
Location of capacitors
Where each value sits: PF₁ → kVAr, φ₁, φ₂, PF · PF₂ → kVAr, φ₁, φ₂, PF
What it means
Raising the PF at the load end lowers the current for the same kW, so the I²R loss in the upstream cables falls by 1 − (old PF ÷ new PF)².
Exam trap. Ratio old ÷ new, then SQUARE it — then subtract from 1.
Maximum demand registered by MD meter
MD = Σ(kVA × minutes) ÷ demand interval (30 min)
Symbols · units
Symbols
kVA of each period; duration in minutes
Answer unit
kVA
Book topic
Maximum demand
Where each value sits: kVA → kVA × minutes / 30-min interval · duration → kVA × minutes / 30-min interval
What it means
The meter averages kVA over each 30-minute window and remembers the highest window of the month. You pay demand charges on that peak even if it happened once.
▶ Try it: Transformer: load it up — iron loss stays flat, copper loss grows with load²
What it means
Iron (no-load) loss is constant whenever the transformer is energised; copper (load) loss rises with the SQUARE of the load. Efficiency is highest where the two are equal.
Worked example. 750 kVA, 1,200 W no-load, 7,200 W full-load Cu, at 60 %: 1,200 + 0.36 × 7,200 = 3,792 W (2025 Q7).
Exam trap. At 60 % load the copper loss is 0.36 × full-load, never 0.6 ×.
Transformer loss at any load (from kVA)
= No-load loss + (actual kVA ÷ rated kVA)² × Full-load loss
Symbols · units
Symbols
kVA; losses in kW or W
Answer unit
kW (or W)
Book topic
Transformer losses
Where each value sits: kVA → kVA, kVAr, kW · losses → kVA, kVAr, kW
▶ Try it: Transformer: load it up — iron loss stays flat, copper loss grows with load²
What it means
Same idea using the actual kVA carried: the load fraction is actual ÷ rated kVA.
Worked example. Rated 1,000 kVA carrying 500 kVA → fraction 0.5 → Cu loss = 0.25 × full-load Cu loss.
Exam trap. Load fraction from kVA, not from kW.
Voltage regulation
% Regulation = (Es − Er) ÷ Er × 100
Symbols · units
Symbols
Es = sending-end voltage, Er = receiving-end voltage (V)
Answer unit
%
Book topic
Voltage regulation
Where each value sits: Es → sending-end Es · Er → receiving-end Er, V
What it means
How much the voltage drops between the sending and receiving end under load, as a percentage of the receiving-end voltage; big drops mean long or overloaded lines.
Worked example. Es 11.5 kV, Er 11.0 → 4.5 %.
Exam trap. Divide by the RECEIVING end voltage (book formula).
Input energy of a distribution area
Ei = Import − Export
Symbols · units
Symbols
energy in MU (million units)
Answer unit
MU
Book topic
AT&C losses
Where each value sits: energy → energy needed at end use
What it means
The energy a DISCOM area actually receives to sell: what it imports minus what it exports to neighbouring areas.
Worked example. Import 12 MU, export 2 MU → 10 MU.
Exam trap. Measured in million units (MU = 10⁶ kWh).
Billing efficiency
BE = Eb ÷ Ei × 100
Symbols · units
Symbols
Eb = total energy billed (MU), Ei = input energy (MU)
Answer unit
%
Book topic
AT&C losses
Where each value sits: Eb → energy billed Eb · Ei → input energy Ei (import − export)
What it means
Share of the input energy that was actually billed to consumers (metered + un-metered). The rest is technical loss plus theft/unbilled use.
Worked example. Billed 7 MU of 10 MU input → 70 % (book Table 1.7).
Exam trap. Include un-metered billed energy (flat-rate agricultural) in the billed figure.
Amount collected without arrears
Ac = AG − Ar
Symbols · units
Symbols
AG = gross amount collected, Ar = arrears collected (Rs)
Answer unit
Rs
Book topic
AT&C losses
Where each value sits: AG → amount billed Ab, collected AG, arrears Ar · Ar → amount billed Ab, collected AG, arrears Ar
What it means
Money collected for THIS year's bills only — arrears belong to earlier years and would inflate the collection efficiency.
Exam trap. If arrears are not given, assume Ar = AG − Ab (book note).
Collection efficiency
CE = Ac ÷ Ab × 100
Symbols · units
Symbols
Ac = amount collected without arrears, Ab = amount billed (Rs)
Answer unit
%
Book topic
AT&C losses
Where each value sits: Ac → amount billed Ab, collected AG, arrears Ar · Ab → energy billed Eb
What it means
Share of the amount billed that was actually paid (this year's bills).
Worked example. 370 ÷ 400 = 92.5 % ≈ 93 %.
Exam trap. Money ratio, not energy.
AT&C (Aggregate Technical & Commercial) loss
AT&C = [1 − (BE × CE)] × 100
Symbols · units
Symbols
BE and CE as fractions
Answer unit
%
Book topic
AT&C losses
Where each value sits: BE → billing efficiency BE
What it means
The DISCOM's total loss: energy lost technically AND commercially (not billed, not collected) as one number — 1 minus the product of the two efficiencies.
Worked example. BE 0.70 × CE 0.93 = 0.651 → AT&C = 34.9 % ≈ 35 % (book). 2025 S-2 asks exactly this chain.
Exam trap. Multiply the two efficiencies as FRACTIONS, then subtract from 1; do not add the two losses.
Total harmonic distortion of current
THD = √(I₃² + I₅² + I₇² + …) ÷ I₁ × 100
Symbols · units
Symbols
I₁ = fundamental current (A); I₃, I₅… = harmonic currents (A)
Answer unit
%
Book topic
Harmonics
Where each value sits: I₁ → I₁ fundamental · I₃ → I₃, I₅, I₇ harmonics · I₅… → I₃, I₅, I₇ harmonics
What it means
How much the current waveform is polluted by frequencies at multiples of 50 Hz (from VFDs, UPS, rectifiers, CFLs). Root-sum-square of the harmonic currents divided by the fundamental.
Worked example. I₁ 250 A, I₃ 50, I₅ 35 → √(2,500 + 1,225) ÷ 250 = 24.4 % (book example).
Exam trap. Square, add, then root — never a plain sum of the harmonic percentages. Resistive loads (heaters) create no harmonics.
Overall efficiency of an energy chain
η overall = η₁ × η₂ × η₃ × …
Symbols · units
Symbols
each efficiency as a fraction
Answer unit
% (or fraction)
Book topic
1 unit saved = 2 units generated
Where each value sits: each → η₁ × η₂ × η₃
What it means
Efficiencies in series multiply. From power station to the motor shaft the book's chain is 0.83 (generation & T&D) × 0.95 × 0.9 × 0.7 ≈ 0.50.
Worked example. Four stages at 83 %, 95 %, 90 %, 70 % → 50 %.
Exam trap. Multiply, do not average.
Energy to be generated for a given end use
= Energy needed at end use ÷ η overall
Symbols · units
Symbols
kWh; η as fraction
Answer unit
kWh
Book topic
1 unit saved = 2 units generated
Where each value sits: kWh → energy needed at end use · η: η as fraction
What it means
Because the chain is only ~50 % efficient, every unit saved at the end use saves about two units at the power station — 'one unit saved = two units generated'.
Worked example. 1 kWh saved at the shaft ÷ 0.5 = 2 kWh of generation avoided.
Exam trap. Divide by the efficiency, never multiply.
Power triangle — what a capacitor does
Transformer losses vs load
Definitions the exam asks
Maximum demand and load factor
MD is the highest 30-minute average kVA in the month; load factor = average load ÷ maximum demand. Improving load factor (shifting loads off-peak) cuts demand charges.
TOD tariff
Time-of-day tariff charges more in peak hours and less off-peak, to encourage shifting load.
Harmonics
Currents at multiples of 50 Hz from non-linear loads (VFDs, UPS, rectifiers, CFLs); they heat transformers, trip breakers and distort voltage. Resistive heaters and incandescent lamps create none.
Automatic PF controller
Switches capacitor steps in and out to hold the target PF as load changes; capacitors at the load end also cut cable losses.
DSM
Demand-side management: the utility shapes customer load — peak clipping, valley filling, load shifting, strategic conservation.
~10 marks: many easy objectives (losses, speed, slip, IE classes) plus the loading and replacement-saving numericals.
Squirrel-cage induction motors with the rotor and cooling fan removedPhoto: Zureks · CC BY-SA 3.0 · sourceVariable-frequency drive — changes motor speed by changing supply frequency (Ns = 120f/P)Photo: Suyash.dwivedi · CC BY-SA 4.0 · source
Synchronous speed
Ns = 120 × f ÷ P
Symbols · units
Symbols
f = supply frequency (Hz), P = number of poles
Answer unit
rpm
Book topic
Motor speed
Where each value sits: f → synchronous speed Ns, poles P · P → synchronous speed Ns, poles P
The speed of the rotating magnetic field; the rotor can never quite reach it. Indian 50 Hz speeds: 3,000 / 1,500 / 1,000 / 750 / 600 / 500 rpm for 2 / 4 / 6 / 8 / 10 / 12 poles.
Exam trap. More poles = slower; poles are always an even number.
Slip
Slip % = (Ns − N) ÷ Ns × 100
Symbols · units
Symbols
Ns = synchronous speed, N = actual full-load speed (rpm)
Answer unit
%
Book topic
Motor speed
Where each value sits: Ns → synchronous speed Ns, poles P · N → rotor speed N, slip
What it means
How far the rotor lags the field, as a percentage. Full-load slip of a good motor is 2–5 %; slip rises with load and with poor rotor design (rewinding damage).
Worked example. Ns 1,500, N 1,470 → 2 %.
Exam trap. Slip is measured at the rated (full-load) speed on the nameplate.
Motor power factor
PF = cos φ = kW ÷ kVA
Symbols · units
Symbols
kW, kVA
Answer unit
no unit
Book topic
Power factor
Where each value sits: kW → input kW · kVA → V, I, cos φ, f
What it means
As load falls the working current drops but the magnetising current does not, so PF collapses at light load — lightly loaded motors are the main cause of poor plant PF.
Worked example. Full load PF 0.85; at 25 % load perhaps 0.5.
Exam trap. Low PF at light load is normal, not a fault.
Motor efficiency
η = P out ÷ P in = 1 − (P loss ÷ P in)
Symbols · units
Symbols
P out = output, P in = input, P loss = losses (kW)
Answer unit
% (or fraction)
Book topic
Motor efficiency
Where each value sits: P out → synchronous speed Ns, poles P · P in → synchronous speed Ns, poles P · P loss → synchronous speed Ns, poles P
What it means
Output at the shaft divided by electrical input; the difference is heat (I²R in stator and rotor, core, friction & windage, stray). Efficiency is flat from 50–100 % load and falls steeply below 40 %.
The electrical power the motor is drawing right now, from measured volts, amps and PF.
Worked example. 410 V, 75 A, PF 0.8 → 1.732 × 0.410 × 75 × 0.8 = 42.6 kW (2023).
Exam trap. Voltage in kV in this form of the formula.
Friction & windage + core loss (no-load test)
= No-load input power − (No-load current)² × Stator resistance
Symbols · units
Symbols
W, A, Ω
Answer unit
W
Book topic
Field tests
Where each value sits: no-load kW → input kW · I no-load → V, I, cos φ, f · R stator → stator I²R, resistance R · F&W + core → losses, F&W, core, stray
What it means
Run the motor unloaded: nearly all the input is core loss plus bearing/fan (friction & windage) loss, after subtracting the small stator I²R at no-load current.
Worked example. No-load 1,064 W, no-load current 10 A, R 0.5 Ω → 1,064 − 100 × 0.5 = 1,014 W.
Exam trap. Subtract the stator I²R at NO-LOAD current, using the per-phase resistance as the book does.
Stator resistance corrected to operating temperature
R₂ = R₁ × (235 + t₂) ÷ (235 + t₁)
Symbols · units
Symbols
R₁ = resistance at ambient t₁ (°C); t₂ = operating temperature (°C)
Answer unit
Ω
Book topic
Field tests
Where each value sits: R₁ → stator I²R, resistance R · t₂ → temperature t₁, t₂
Copper resistance rises with temperature; the resistance measured cold must be scaled to the running temperature (100–120 °C for modern motors) before calculating I²R loss.
Worked example. R at 30 °C = 0.5 Ω → at 120 °C: 0.5 × (235 + 120)/(235 + 30) = 0.67 Ω.
Exam trap. The constant 235 belongs to copper; it is added to BOTH temperatures.
~20 marks: FAD, leakage, specific power and receiver/pipe sizing numericals; intercooling and dryer theory.
Small reciprocating (piston) air compressor with its receiverPhoto: Sirotmusic · CC BY-SA 4.0 · sourceLarge two-stage reciprocating compressor — intercooling between stages cuts the workPhoto: Chris Allen · CC BY-SA 2.0 · sourceAir receiver — stores air, smooths demand peaks and separates moisturePhoto: P1898 · CC BY 4.0 · sourceCompressed-air system layout: compressor, after-cooler, receiver, dryer, distributionPhoto: Brian S. Elliott · CC BY-SA 4.0 · source
Compressor displacement
= (π ÷ 4) × D² × L × S × X × n
Symbols · units
Symbols
D = bore (m), L = stroke (m), S = speed (rpm), X = 1 single / 2 double acting, n = no. of cylinders
Answer unit
m³/min
Book topic
Volumetric efficiency
Where each value sits: D → bore D, stroke L, speed S, X, n · L → bore D, stroke L, speed S, X, n · S → bore D, stroke L, speed S, X, n · X → bore D, stroke L, speed S, X, n · n → bore D, stroke L, speed S, X, n
Exam trap. Absolute pressures and Q in m³/HOUR in this book formula.
Isothermal efficiency
= Isothermal power ÷ Actual measured input power × 100
Symbols · units
Symbols
kW
Answer unit
%
Book topic
Isothermal efficiency
Where each value sits: kW → input kW, isothermal kW, SPC
What it means
Ideal power divided by what the compressor and motor actually draw — the reported compressor efficiency (typically 60–70 %).
Worked example. 35 kW ideal ÷ 55 kW actual = 64 %.
Exam trap. It is lower than adiabatic efficiency for the same machine — the book warns about comparing vendors' numbers.
Free air delivery by pump-up test
Q = [(P₂ − P₁) ÷ P₀] × V ÷ T
Symbols · units
Symbols
P₂ final, P₁ initial, P₀ atmospheric (kg/cm² abs); V = receiver + pipe volume (m³); T = time (min)
Answer unit
m³/min
Book topic
Capacity assessment
Where each value sits: P₂ → receiver V, P₁ → P₂, time T · P₁ → receiver V, P₁ → P₂, time T · P₀ → P₁ intake, P₂ delivery, r = P₂/P₁ · V → receiver V, P₁ → P₂, time T · T → T load, t unload
What it means
Shop-floor capacity test: isolate the receiver, time how long the compressor takes to raise its pressure from P₁ to P₂; the air delivered is the receiver volume times the pressure rise in atmospheres, per minute.
Worked example. V 5 m³, P₂ 8 kg/cm² a, P₁ 1 kg/cm² a, P₀ 1.03, T 5 min → (7/1.03) × 5 ÷ 5 = 6.8 m³/min.
Exam trap. Use ABSOLUTE pressures and include the pipe volume up to the isolation valve.
Leakage % (load–unload test)
= T ÷ (T + t) × 100
Symbols · units
Symbols
T = load (on) time, t = unload (off) time — same units
Answer unit
%
Book topic
Leakage test
Where each value sits: T → T load, t unload · t → T load, t unload
▶ Try it: Compressed air: load and unload times → leakage
What it means
With no consumers connected, the compressor still loads periodically to replace leaked air; the fraction of time it spends loaded is the leakage fraction.
Worked example. Load 1.5 min, unload 10.5 min → 1.5/12 = 12.5 %. 200 cfm, load 10 s / unload 20 s → 67 cfm leakage (2023).
Exam trap. T (load) on top, T + t below.
Leakage quantity
q = Q × T ÷ (T + t)
Symbols · units
Symbols
Q = compressor capacity (m³/min)
Answer unit
m³/min
Book topic
Leakage test
Where each value sits: Q → FAD Q, displacement
▶ Try it: Compressed air: load and unload times → leakage
What it means
Leakage in flow units = compressor capacity × leakage fraction.
Worked example. 500 cfm × 0.125 = 62.5 cfm.
Exam trap. Same units as the capacity.
Specific power consumption
= Power (kW) ÷ FAD (m³/min)
Symbols · units
Symbols
kW, m³/min
Answer unit
kW per m³/min
Book topic
Performance
Where each value sits: kW → input kW, isothermal kW, SPC · m³/min → FAD Q, displacement
▶ Try it: Chiller: flow and temperature drop of chilled water → tons of refrigeration
What it means
kW per unit of air delivered — the efficiency benchmark of a compressed-air system (typical 0.15–0.20 kW/cfm... in book units ≈ 6–8 kW per m³/min).
Worked example. 370 kW ÷ 2,392 m³/min... (book: 0.155 kW/m³).
Exam trap. Keep kW and flow in the same basis (per minute or per hour).
Power wasted in leakage
= Leakage quantity × Specific power consumption
Symbols · units
Symbols
m³/min × kW per m³/min
Answer unit
kW
Book topic
Leakage test
Where each value sits: m³/min → input kW, isothermal kW, SPC
What it means
Leaked air cost you the power to compress it: leakage flow × specific power.
~23 marks (top chapter): TR, COP, kW/TR numericals every year; VCR vs VAM, refrigerants, psychrometry and ventilation.
Water-cooled centrifugal chiller — evaporator and condenser shells with the compressor on topPhoto: P199 · Public domain · sourceSling psychrometer — wet-bulb and dry-bulb thermometers give relative humidityPhoto: User:CambridgeBayWeather · Public domain · source
Refrigeration load from chilled water
TR = Q × Cp × (Ti − To) ÷ 3024
Symbols · units
Symbols
Q = coolant flow (kg/hr), Cp (kcal/kg °C), Ti, To = inlet, outlet temperature (°C)
Answer unit
TR
Book topic
Performance assessment
Where each value sits: Q → Q flow kg/hr, Cp, Ti, To → TR · Cp → Q flow kg/hr, Cp, Ti, To → TR · Ti → Q flow kg/hr, Cp, Ti, To → TR · To → Q flow kg/hr, Cp, Ti, To → TR · outlet: outlet temperature (°C)
Exam trap. The exam sometimes asks for compressor kW/TR only — read which.
Coefficient of performance
COP = Refrigeration effect ÷ Power input
Symbols · units
Symbols
both in the same units (kW ÷ kW)
Answer unit
no unit
Book topic
COP
Where each value sits: both → power input kW, W
▶ Try it: Chiller: flow and temperature drop of chilled water → tons of refrigeration
What it means
Cooling produced per unit of work input, both in the same units. Higher COP = more efficient. Typical VCR 3–5; single-effect VAM ≈ 0.65–0.7.
Worked example. Cooling 3.517 kW per TR at 1.7 kW/TR → COP 2.07 (2018/2021).
Exam trap. Same units top and bottom (kW ÷ kW, or kcal ÷ kcal).
COP from kW/TR
COP = 3.51 ÷ (kW/TR)
Symbols · units
Symbols
1 TR = 3.51 kW
Answer unit
no unit
Book topic
COP
Where each value sits: 1 TR → Q flow kg/hr, Cp, Ti, To → TR
▶ Try it: Chiller: flow and temperature drop of chilled water → tons of refrigeration
What it means
Because 1 TR = 3.51 kW of cooling, COP is simply 3.51 divided by the kW/TR.
Worked example. 0.7 kW/TR → COP 5.0.
Exam trap. Use 3.51 (kW), not 3,024 (kcal/hr) with kW.
Carnot COP
COP = Te ÷ (Tc − Te)
Symbols · units
Symbols
Te = evaporator, Tc = condenser temperature (K = °C + 273)
Answer unit
no unit
Book topic
COP
Where each value sits: Te → Te evaporator · Tc → heat rejected, Tc
What it means
The theoretical best for the two temperatures; shows why a HIGHER evaporator temperature and LOWER condenser temperature raise efficiency (≈ 2–3 % per °C).
Worked example. Te 5 °C (278 K), Tc 40 °C (313 K) → 278 ÷ 35 = 7.9.
Exam trap. Kelvin — add 273 to both.
Energy efficiency ratio (star label)
EER = Refrigeration effect (W) ÷ Power input (W)
Symbols · units
Symbols
W, W
Answer unit
W/W
Book topic
Room AC labelling
Where each value sits: W → power input kW, W · W → power input kW, W
Qe = waste heat taken in (kW), W = compressor work (kW)
Answer unit
kW
Book topic
Heat pumps
Where each value sits: Qe → Q flow kg/hr, Cp, Ti, To → TR · W → power input kW, W
What it means
A heat pump is a refrigerator used for its hot side: it delivers the waste heat it absorbed plus the compressor work, so heating COP is always > 1.
Worked example. Absorbs 100 kW at 20 kW work → delivers 120 kW (COP 6 heating).
Exam trap. Heating COP = cooling COP + 1.
Ventilation rate
Q = L × B × H × ACH
Symbols · units
Symbols
L, B, H = room size (m), ACH = air changes per hour
Answer unit
m³/hr
Book topic
Ventilation
Where each value sits: L → air flow, ρ, h in/out, ACH, L×B×H · B → air flow, ρ, h in/out, ACH, L×B×H · H → air flow, ρ, h in/out, ACH, L×B×H · ACH → air flow, ρ, h in/out, ACH, L×B×H
What it means
Air changes per hour times the room volume gives the fan duty for ventilating a room (compressor rooms 10–20 ACH, engine rooms 20).
Worked example. 15 × 10 × 4 m room at 10 ACH = 6,000 m³/hr (book); 15 × 10 × 4 at 20 ACH = 12,000 m³/hr (2018/2022 objective).
Exam trap. ACH is per HOUR; divide by 3,600 for m³/s.
Water added in humidification
m = V × ρ × (w₂ − w₁)
Symbols · units
Symbols
V = air flow (m³/hr), ρ (kg/m³), w = specific humidity (kg/kg dry air)
Answer unit
kg/hr
Book topic
Humidification
Where each value sits: V → Q flow kg/hr, Cp, Ti, To → TR · ρ → air flow, ρ, h in/out, ACH, L×B×H · w → power input kW, W
What it means
Spraying water into air raises its moisture content; the water needed is the air mass flow times the rise in specific humidity.
Exam trap. This is a check figure, not a formula to derive.
Vapour-compression cycle
Psychrometric chart basics
Definitions the exam asks
Vapour compression vs absorption
VCR: compressor (electrical) drives the cycle, COP 3–5. VAM: generator (heat) drives it with absorbent LiBr or water-ammonia, COP 0.65–1.2, uses waste heat/steam. Ammonia is the refrigerant common to both; 'generator' is the VAM part that is NOT in VCR; 'absorber' likewise.
Refrigerants
CFCs (R-11, R-12) phased out for ozone; HCFC R-22 being phased out; HFC R-134a; natural: ammonia (R-717), CO₂, hydrocarbons.
Chilled-water temperature
Raising the chilled-water leaving temperature by 1 °C improves compressor efficiency ≈ 3 %; lowering condenser temperature does the same.
Psychrometry terms
DBT, WBT, RH, dew point, specific humidity, enthalpy; when DBT = WBT the air is saturated.
Star labelling of room ACs
Based on EER (W/W) at standard test conditions; higher EER = more stars.
~11 marks: fan laws (power ∝ N³) and static-efficiency numericals; fan types, dampers vs VFD, ASME classification.
Industrial centrifugal fan on its motor basePhoto: SAF · CC BY-SA 4.0 · sourceAxial-flow fan — air enters and leaves along the shaft with no change of directionPhoto: Bobbie4 (talk) · Public domain · sourcePitot-static tube — measures velocity pressure for duct flowPhoto: Z22 · CC BY-SA 3.0 · source
ASME specific ratio
SR = Discharge pressure ÷ Suction pressure
Symbols · units
Symbols
absolute pressures
Answer unit
no unit (fan ≤ 1.11, blower 1.11–1.20, compressor > 1.20)
Exam trap. Density at the FLOW temperature, not at 0 °C.
Gas density (ideal gas)
γ = P × M ÷ (R × T)
Symbols · units
Symbols
P = absolute pressure (mmWC), M = mol. weight (air 28.92), R = 847.84 mmWC·m³/kg-mole·K, T (K)
Answer unit
kg/m³
Book topic
Flow measurement
Where each value sits: P → gas density γ, T, M · M → gas density γ, T, M · R → gas density γ, T, M · m³/kg-mole → gas density γ, T, M · K: K · T → gas density γ, T, M
What it means
Density falls as the gas gets hotter or the pressure drops; needed before velocity and mass-flow calculations for hot flue gas.
Worked example. Air at 10,330 mmWC, 311 K: 10,330 × 28.92 ÷ (847.84 × 311) = 1.133 kg/m³.
Exam trap. Absolute pressure in mmWC and T in kelvin with R = 847.84.
Air density at t °C
γ = 1.293 × 273 ÷ (273 + t)
Symbols · units
Symbols
1.293 kg/m³ at 0 °C; t (°C)
Answer unit
kg/m³
Book topic
Flow measurement
Where each value sits: 1.293: 1.293 kg/m³ at 0 °C · t → gas density γ, T, M
What it means
Quick correction from the standard 1.293 kg/m³ at 0 °C.
Worked example. At 38 °C: 1.293 × 273/311 = 1.135 kg/m³.
~18 marks: pump power (ρgQH), efficiency and affinity/impeller-trimming numericals; throttling vs VFD; NPSH and cavitation.
Close-coupled centrifugal pumps with pressure gauges on suction and dischargePhoto: Saud · CC BY-SA 4.0 · sourceLarge centrifugal pump — impeller casing (volute) and suction inletPhoto: Bernard S. Janse · CC BY 2.5 · source
Hydraulic power
Ph = Q × (hd − hs) × ρ × g ÷ 1000
Symbols · units
Symbols
Q (m³/s), hd = discharge head, hs = suction head (m), ρ (kg/m³), g = 9.81 m/s²
Answer unit
kW
Book topic
Pump power
Where each value sits: Q → pipe: flow Q · hd → discharge head hd · hs → suction head hs · ρ → liquid ρ · g → g = 9.81 m/s²
▶ Try it: Pump: change flow and head — watch the water rise and the power change
What it means
The power actually given to the water: how much flows (Q) times how high it is lifted (head) times the weight of water. This is the useful output of the pump.
Worked example. Q 0.0888 m³/s, H 32 m, water: 0.0888 × 32 × 1000 × 9.81 ÷ 1000 = 27.9 kW (book example).
Exam trap. Q in m³/SECOND (m³/hr ÷ 3600); head in metres of the liquid pumped.
Pump shaft power
Ps = Ph ÷ η pump
Symbols · units
Symbols
kW; η as fraction
Answer unit
kW
Book topic
Pump power
Where each value sits: Ph → hydraulic power Ph · η pump → pump η · Ps → shaft power Ps
▶ Try it: Pump: change flow and head — watch the water rise and the power change
What it means
What the pump needs at its shaft; larger than hydraulic power because of the pump's own losses.
Worked example. 27.9 kW ÷ 0.61 = 45.7 kW.
Exam trap. Divide by efficiency (a fraction), do not multiply.
Motor input power
= Ps ÷ η motor
Symbols · units
Symbols
kW; η as fraction
Answer unit
kW
Book topic
Pump power
Where each value sits: Ps → shaft power Ps · η motor → motor η, input kW · input kW → motor η, input kW
What it means
What the electricity meter sees: shaft power plus the motor's losses.
Worked example. 45.7 ÷ 0.9 = 50.7 kW.
Exam trap. Two efficiencies in series: hydraulic ÷ η_pump ÷ η_motor.
Pump efficiency
η pump = Ph ÷ Ps × 100
Symbols · units
Symbols
kW
Answer unit
%
Book topic
Pump power
Where each value sits: Ph → hydraulic power Ph · Ps → shaft power Ps · η → pump η
▶ Try it: Pump: change flow and head — watch the water rise and the power change
What it means
Useful water power divided by the shaft power; measured in an audit from flow, head and motor kW (× motor efficiency).
Worked example. Hydraulic 27.9 kW; motor 50.7 kW at 90 % → shaft 45.6 → η = 61 % (book). 2024 S-6: 5 m suction + 30 m discharge, 150 m³/hr, 18 kW motor at 85 % → 15.3 kW shaft → η ≈ 93 %... check numbers in the paper.
Exam trap. Use SHAFT power (motor kW × motor η), not motor input, or you understate efficiency.
Head from a pressure-gauge reading (water)
Head (m) = Pressure (kg/cm²) × 10
Symbols · units
Symbols
kg/cm²
Answer unit
m
Book topic
Pump head
Where each value sits: kg/cm² → pressure gauge kg/cm²
What it means
A pressure gauge in kg/cm² converts to metres of water column at about 10 m per kg/cm²; add suction lift (or subtract positive suction head) to get total head.
Worked example. Discharge 2.6 kg/cm² = 26 m; water 4 m BELOW pump centreline → total head 30 m (2013 exam). 3.0 kg/cm² with +5 m positive suction → 30 − 5 = 25 m (2024).
Exam trap. Suction lift ADDS to head; positive suction head SUBTRACTS.
Worked example. Speed halved → head 100 m → 25 m (book).
Exam trap. Square.
Affinity law – power and speed
kW₁ ÷ kW₂ = (N₁ ÷ N₂)³
Symbols · units
Symbols
N (rpm)
Answer unit
kW
Book topic
Affinity laws
Where each value sits: N → speed N, impeller D
▶ Try it: Fan laws: slow the fan down — power falls with the CUBE of speed
What it means
Power varies with the CUBE of speed — halving speed needs one-eighth of the power; two-thirds speed ≈ 30 %.
Worked example. 40 kW at 3000 rpm → 5 kW at 1500 rpm (book).
Exam trap. Cube the ratio of speeds, not the ratio of flows squared.
Impeller trimming – flow
Q₁ ÷ Q₂ = D₁ ÷ D₂
Symbols · units
Symbols
D = impeller diameter (mm)
Answer unit
m³/hr
Book topic
Impeller trimming
Where each value sits: D → speed N, impeller D
What it means
Trimming the impeller diameter reduces flow in proportion — a one-time, cheap fix for an oversized pump that is throttled.
Worked example. Flow 150 → 110 m³/hr needs D = 230 × 110/150 = 169 mm (2018/2024 objective).
Exam trap. Trim only down to ~75 % of the original diameter; beyond that efficiency collapses.
Impeller trimming – head
H₁ ÷ H₂ = (D₁ ÷ D₂)²
Symbols · units
Symbols
D (mm)
Answer unit
m
Book topic
Impeller trimming
Where each value sits: D → speed N, impeller D
What it means
Head falls with the square of the diameter ratio.
Worked example. D ratio 0.9 → head 81 %.
Exam trap. Square.
Impeller trimming – power
P₁ ÷ P₂ = (D₁ ÷ D₂)³
Symbols · units
Symbols
D (mm)
Answer unit
kW
Book topic
Impeller trimming
Where each value sits: D → speed N, impeller D
What it means
Power falls with the cube of the diameter ratio — the saving from trimming.
Worked example. D ratio 0.9 → power 73 %.
Exam trap. Cube.
Friction head at a new flow
h₂ = h₁ × (Q₂ ÷ Q₁)²
Symbols · units
Symbols
friction head (m) varies with the square of flow
Answer unit
m
Book topic
System curve
Where each value sits: friction → pipe: flow Q
What it means
Pipe friction losses rise with the square of flow; static head (the lift) does not change. This is why the system curve is a parabola sitting on the static head.
Worked example. Friction 15 m at 100 m³/hr → at 80 m³/hr: 15 × 0.64 = 9.6 m; static 10 m stays 10 m (2011 objective).
Exam trap. Static head is constant; ONLY the friction part scales with Q².
Pump curve, system curve and speed control
Definitions the exam asks
System curve
Static head (constant) plus friction head (∝ Q²); the pump runs where its curve meets the system curve.
Throttling vs speed control
A throttled valve adds resistance and wastes the head; reducing speed moves the pump curve down — power falls with N³. Throttled > 30 % → trim impeller or fit a VFD.
NPSH and cavitation
Net positive suction head available must exceed the pump's required NPSH; otherwise vapour bubbles form and collapse (cavitation). Larger suction pipe, lower liquid temperature and lower suction lift raise NPSHa.
Pumps in series / parallel
Series adds head (shut-off head doubles for two identical pumps); parallel adds flow (shut-off head unchanged).
By-pass lines
Small by-pass lines protect the pump against overheating at very low or zero flow.
Chapter 7 · Cooling Tower
~13 marks: range/approach/effectiveness, evaporation, COC and blowdown numericals recur; L/G ratio and fill types.
Induced-draft cooling tower cells with fans on topPhoto: Cenk Endustri · CC BY-SA 3.0 · sourceFill media inside a cooling tower — where water film meets the airPhoto: SAF · CC BY-SA 4.0 · sourceNatural-draft (hyperbolic) cooling tower seen from insidePhoto: TJBlackwell · CC BY 3.0 · source
Range
= T₁ − T₂ (CW inlet hot − CW outlet cold)
Symbols · units
Symbols
water temperatures (°C)
Answer unit
°C
Book topic
Performance
Where each value sits: T₁ → T₁ hot water in · T₂ → T₂ cold water out · range → range = T₁ − T₂
▶ Try it: Cooling tower: move the temperatures — range, approach and effectiveness
What it means
How much the tower cools the water — set by the PROCESS heat load and flow, not by the tower.
Worked example. Hot 43 °C in, 35 °C out → range 8 °C.
Exam trap. Range is water-to-water.
Approach
= CW outlet (cold) temperature − Ambient wet-bulb temperature
Symbols · units
Symbols
°C
Answer unit
°C
Book topic
Performance
Where each value sits: T₂ → T₂ cold water out · WBT → wet-bulb temperature · approach → approach = T₂ − WBT
▶ Try it: Cooling tower: move the temperatures — range, approach and effectiveness
What it means
How close the cold water gets to the air's wet-bulb temperature — the true measure of tower performance; lower approach = better (and bigger, costlier) tower.
Worked example. Cold water 32.2 °C, WBT 26.7 → approach 5.5 °C (book).
Exam trap. Approach uses the WET-bulb of the ambient air, not the dry-bulb, and not the inlet water.
Cooling tower effectiveness
= Range ÷ (Range + Approach) × 100
Symbols · units
Symbols
°C
Answer unit
%
Book topic
Performance
Where each value sits: range → range = T₁ − T₂ · approach → approach = T₂ − WBT
▶ Try it: Cooling tower: move the temperatures — range, approach and effectiveness
What it means
Range as a share of the ideal range (hot water to wet-bulb); 100 % would mean the water reached the wet-bulb.
Worked example. Range 8, approach 5.5 → 8 ÷ 13.5 = 59 %.
Exam trap. Denominator is range PLUS approach.
Cooling capacity (heat rejected)
= m × Cp × (T₁ − T₂)
Symbols · units
Symbols
m = water flow (kg/hr = m³/hr × 1000), Cp = 1 kcal/kg °C
Answer unit
kcal/hr (÷ 3024 = TR)
Book topic
Performance
Where each value sits: m → circulation rate m³/hr, m, Cp · Cp → circulation rate m³/hr, m, Cp
What it means
The heat the tower throws away = water flow × 1 kcal/kg °C × range; divide by 3,024 for TR.
▶ Try it: Cooling tower water: raise the cycles of concentration — blowdown falls
What it means
Cooling happens mainly by evaporating about 1 % of the water for every 5.5–6 °C of range; this water is lost and must be made up.
Worked example. 1,000 m³/hr, range 8: 0.00085 × 1.8 × 1,000 × 8 = 12.2 m³/hr (≈ 1.2 %).
Exam trap. Multiply by BOTH constants 0.00085 and 1.8 (book form).
Cycles of concentration
COC = Dissolved solids in circulating water ÷ Dissolved solids in make-up water
Symbols · units
Symbols
ppm (or conductivity)
Answer unit
no unit
Book topic
Water losses
Where each value sits: TDS circulating → circulation rate m³/hr, m, Cp · TDS make-up → make-up = E + B + D · COC → blowdown B, COC
▶ Try it: Cooling tower water: raise the cycles of concentration — blowdown falls
What it means
Because only pure water evaporates, dissolved solids build up; COC says how many times more concentrated the circulating water is than the make-up. Higher COC = less blowdown = less water, until scaling limits it.
Mass of water per mass of air through the tower; the heat lost by the water equals the heat gained by the air, so L/G = enthalpy rise of air ÷ temperature drop of water. Typical 0.75–1.5.
Worked example. Air enthalpy in 20, out 30 kcal/kg; water 43 → 35: L/G = 10 ÷ 8 = 1.25.
Exam trap. It is MASS flow of water ÷ MASS flow of air (2015/2018 objective), not volume.
Air mass flow
= Air volume flow × Air density
Symbols · units
Symbols
m³/hr × kg/m³
Answer unit
kg/hr
Book topic
L/G ratio
Where each value sits: m³/hr → circulation rate m³/hr, m, Cp
What it means
Fan air volume × air density; needed to compute L/G.
Exam trap. Density of hot humid air ≈ 1.08, not 1.2.
% evaporation loss
= Evaporation ÷ Circulation rate × 100
Symbols · units
Symbols
m³/hr
Answer unit
%
Book topic
Water losses
Where each value sits: m³/hr → circulation rate m³/hr, m, Cp
What it means
Evaporation as a share of circulation — a sanity check (about 1 % per 6 °C of range).
Worked example. 12.2 ÷ 1,000 = 1.2 %.
Range, approach and effectiveness
Cooling-tower water balance
Definitions the exam asks
Tower types
Natural draft (hyperbolic, power plants) and mechanical draft — forced (fan at inlet) or induced (fan at top, most common in industry); counter-flow vs cross-flow.
Fill
Splash fill (droplets, 30–45 m²/m³) and film fill (thin film over sheets, 150 m²/m³, more efficient but fouls).
Drift eliminator
Captures water droplets carried out in the air stream leaving the tower.
Factors affecting performance
Wet-bulb temperature, range, approach, heat load, L/G ratio, fill condition, water distribution. If heat load, range and WBT are fixed, a smaller approach needs a bigger tower.
Book performance norms
Approach 2.8–5.5 °C typical; % evaporation ≈ 1 % per 6 °C range.
Street-light luminaire (HPSV/LED) — luminaire distributes and controls the lamp's lightPhoto: Bidgee · CC BY 3.0 · sourceCompact fluorescent lampsPhoto: SecretDisc · CC BY-SA 3.0 · sourceTubular lamps — T-number gives the tube diameter in eighths of an inchPhoto: Dmitry G · CC BY-SA 3.0 · source
Illuminance – inverse square law
E = I ÷ d²
Symbols · units
Symbols
I = luminous intensity of the source (book writes it in lumens), d = distance (m)
Answer unit
lux (lm/m²)
Book topic
Basic terms
Where each value sits: I → lamp: lumens F, watts, efficacy lm/W · d → mounting height Hm, distance d
Where each value sits: lumen → lamp: lumens F, watts, efficacy lm/W · m²: m²
What it means
One lumen of light spread over one square metre. Offices need ~300–500 lux, corridors ~100, precision work 1,000+.
Worked example. 300 lux on 216 m² needs 64,800 lumens (2025 S-1).
Exam trap. Lux is per m²; lumen is the total light output.
Luminous efficacy
= Luminous flux (lm) ÷ Lamp power (W)
Symbols · units
Symbols
lm, W
Answer unit
lm/W
Book topic
Basic terms
Where each value sits: lm → lamp: lumens F, watts, efficacy lm/W · W → lamp: lumens F, watts, efficacy lm/W
What it means
Lumens of light per watt of electricity — the efficiency of a lamp. Ranking: LPSV > HPSV ≈ LED > metal halide > CFL > FTL > HPMV > halogen > incandescent.
Worked example. 18 W LED tube giving 1,800 lm → 100 lm/W.
Exam trap. Efficacy is a property of the LAMP; circuit efficacy includes the ballast/driver.
Maximum possible luminous efficacy
1 W = 683 lm at 555 nm
Symbols · units
Symbols
—
Answer unit
lm/W
Book topic
Basic terms
Where each value sits: 683 lm/W → lamp: lumens F, watts, efficacy lm/W · 555 nm → lamp: lumens F, watts, efficacy lm/W
What it means
If every watt became visible green light at 555 nm (the eye's peak sensitivity) you would get 683 lm — the physical ceiling.
Worked example. A 100 lm/W lamp is 15 % of the maximum.
Exam trap. 683 lm/W at 555 nm, not white light.
Installed load efficacy (ILE)
= Average maintained illuminance (lux) ÷ Installed power density (W/m²)
Symbols · units
Symbols
lux, W/m²
Answer unit
lux/W/m²
Book topic
Basic terms
Where each value sits: lux → illuminance E lux, area A · W/m² → lamp: lumens F, watts, efficacy lm/W
What it means
How much illuminance you get per watt per square metre — judges the whole installation (lamps + luminaires + layout), not just the lamp.
Worked example. 300 lux at 12 W/m² → 25 lux per W/m².
Exam trap. Higher ILE = better installation.
Installed power density (lighting power density)
= Total lighting load (W) ÷ Floor area (m²)
Symbols · units
Symbols
W, m²
Answer unit
W/m² (book: per 100 lux)
Book topic
Basic terms
Where each value sits: W → lamp: lumens F, watts, efficacy lm/W · m²: m²
What it means
Watts of lighting per square metre of floor; ECBC limits it (e.g. offices ≈ 10.8 W/m², Ch10).
Worked example. 2.1 kW over 200 m² = 10.5 W/m².
Exam trap. The book also quotes it 'per 100 lux' for comparison between spaces.
A shape factor: big low rooms have a high index (light reaches the work plane easily); tall narrow rooms a low one. It is looked up against the luminaire's utilisation factor table.
Worked example. 10 × 10 m room, mounting height 2.0 m → 100 ÷ (2 × 20) = 2.5 (book).
Exam trap. Mounting height is luminaire height ABOVE THE WORK PLANE, not above the floor.
Mounting height
Hm = Luminaire height − Work-plane height
Symbols · units
Symbols
m
Answer unit
m
Book topic
Lighting design
Where each value sits: luminaire ht → lamp: lumens F, watts, efficacy lm/W · work-plane ht → illuminance E lux, area A · Hm → mounting height Hm, distance d
What it means
Distance from the luminaire down to the work plane (desk height ≈ 0.8–0.9 m).
Worked example. Luminaire at 2.9 m, work plane 0.9 m → 2.0 m (book).
Lamps dim with age, luminaires and room surfaces get dirty; LLF (≈ 0.7–0.8) allows for this so the design still meets the lux at maintenance time.
Worked example. 0.9 × 0.9 × 0.9 = 0.73.
Exam trap. Multiply the three maintenance factors.
Number of fittings required
N = (E × A) ÷ (F × UF × LLF)
Symbols · units
Symbols
E = required lux, A = area (m²), F = lumens per fitting, UF = utilisation factor
Answer unit
number
Book topic
Lighting design
Where each value sits: E → illuminance E lux, area A · A → illuminance E lux, area A · F → lamp: lumens F, watts, efficacy lm/W · UF → room L × W, room index, UF, LLF
What it means
The lumen method: total lumens needed ÷ lumens each fitting actually delivers to the work plane.
Worked example. 216 m² at 300 lux, 18 W LED tubes of 1,800 lm, UF 0.5, LLF 0.8: N = 64,800 ÷ (1,800 × 0.5 × 0.8) = 90 tubes (2025 S-1 pattern).
Exam trap. F is lumens per FITTING (twin-tube = 2 lamps); round UP.
Space-to-height ratio
SHR = Spacing between luminaires ÷ Mounting height
Symbols · units
Symbols
m ÷ m
Answer unit
no unit
Book topic
Lighting design
Where each value sits: spacing → spacing, SHR · Hm → mounting height Hm, distance d
What it means
Spacing between luminaires divided by mounting height; keep at or below the luminaire's recommended value (≈ 1.5) for uniform light.
Worked example. Spacing 3 m, height 2 m → 1.5.
Exam trap. Exceeding it gives dark patches between fittings.
Uniformity ratio
= Minimum illuminance ÷ Average illuminance
Symbols · units
Symbols
lux
Answer unit
no unit
Book topic
Lighting design
Where each value sits: lux → illuminance E lux, area A
What it means
Minimum lux ÷ average lux on the work plane; aim ≥ 0.7.
~11 marks: SFC and efficiency numericals, loss split (exhaust largest), waste-heat recovery, sizing with diversity factor.
Packaged diesel generator set in an acoustic enclosurePhoto: Gregsedits · CC BY-SA 3.0 · sourceDiesel engine coupled to its alternatorPhoto: Wikimedia Commons · CC BY-SA 3.0 · source
Real power of a DG set
kW = kVA × PF
Symbols · units
Symbols
kVA, PF
Answer unit
kW
Book topic
DG basics
Where each value sits: kVA → kVA rating, BHP × 0.746 · PF → kW = kVA × PF, units generated
Exam trap. Convert litres to kg with the density before applying GCV.
Waste heat recoverable from exhaust
= kWh/hr × 8 kg gas/kWh × 0.25 kcal/kg °C × (T exhaust − T out)
Symbols · units
Symbols
temperatures (°C)
Answer unit
kcal/hr
Book topic
Waste heat recovery
Where each value sits: kWh/hr → kW = kVA × PF, units generated · 8 kg/kWh → exhaust: 8 kg/kWh, Cp 0.25, T in/out · 0.25 → exhaust: 8 kg/kWh, Cp 0.25, T in/out · T exhaust − T out → exhaust: 8 kg/kWh, Cp 0.25, T in/out
What it means
Exhaust gas (≈ 8 kg per kWh at ≈ 450 °C) can heat water or make steam down to about 180 °C; the recoverable heat is mass × Cp × temperature drop.
~15 marks: ECBC applicability, envelope terms (WWR, EA, SHGC, U-factor), EPI/star rating, LPD — the 2025 long question was a full EPI/LPD/diversity calculation.
Office façade — window-wall ratio, SHGC and VLT of the glazing decide the cooling load and daylightPhoto: Calderoliver · CC BY-SA 3.0 · sourceBuilding envelope: glazing and shadingPhoto: Jon Rawlinson · CC BY 2.0 · source
Energy Performance Index
EPI = Annual energy consumption ÷ Built-up area
Symbols · units
Symbols
kWh/year, m²
Answer unit
kWh/m²/year
Book topic
Star rating of buildings
Where each value sits: kWh/year → annual kWh, built-up area m² → EPI · m²: m²
Where each value sits: EPI → reflectance + absorptance = 1, emissivity e · hours → hours/day × days/week × 52 → AAhEPI
What it means
BPOs run round the clock, so their EPI is normalised by operating hours: watt-hours per m² per operating hour.
Worked example. EPI 250 kWh/m²/yr, 24 h × 7 d × 52 = 8,736 h → 250 × 1000 ÷ 8,736 = 28.6 (Wh/m²)/hr.
Exam trap. Unit is (Wh/sqm)/hr (book Q9).
Window-wall ratio
WWR = Vertical fenestration area ÷ Gross exterior wall area
Symbols · units
Symbols
m², m²
Answer unit
no unit (or %)
Book topic
Building envelope
Where each value sits: fenestration area → fenestration area, WWR, VLT, SHGC, U · gross wall area → gross exterior wall area · WWR → fenestration area, WWR, VLT, SHGC, U
What it means
How much of the outside wall is glass; more glass = more daylight but more solar heat gain.
Worked example. 60 m² window in 150 m² wall → 0.40.
Exam trap. Gross exterior wall area in the denominator (2022 objective).
Effective aperture
EA = VLT × WWR
Symbols · units
Symbols
no units
Answer unit
no unit (complies if EA ≥ 0.1)
Book topic
Building envelope
Where each value sits: VLT → fenestration area, WWR, VLT, SHGC, U · WWR → fenestration area, WWR, VLT, SHGC, U · EA ≥ 0.1 → fenestration area, WWR, VLT, SHGC, U
What it means
Daylight potential = how much wall is glass × how much light the glass passes; ECBC wants EA ≥ 0.1 so daylight can replace lighting.
Worked example. WWR 0.4 × VLT 0.26 = 0.104 → complies; 0.6 × 0.15 = 0.09 → does not (book cases, 2023 S-3).
Exam trap. Both factors are fractions; compare with 0.1.
Visible light transmittance
VLT = Light through glazing ÷ Light through perfectly transmissive glazing
Symbols · units
Symbols
—
Answer unit
no unit (0 to 1)
Book topic
Building envelope
Where each value sits: light through glazing → fenestration area, WWR, VLT, SHGC, U · VLT → fenestration area, WWR, VLT, SHGC, U
What it means
Share of visible light the glazing lets through (clear glass ≈ 0.8, tinted 0.2–0.5).
Worked example. VLT 0.5 passes half the daylight.
Exam trap. Not the same as SHGC — VLT is light, SHGC is heat.
Solar heat gain coefficient
SHGC = Solar heat gain through fenestration ÷ Incident solar radiation
Symbols · units
Symbols
—
Answer unit
no unit (0 to 1)
Book topic
Building envelope
Where each value sits: solar gain through glass → fenestration area, WWR, VLT, SHGC, U · incident radiation → incident solar radiation, gain W/m² · SHGC → fenestration area, WWR, VLT, SHGC, U
What it means
Share of the sun's heat that gets through the window (directly plus re-radiated). SHGC 0.30 means 30 % of incident solar heat enters; the rest is reflected or re-emitted outside.
Worked example. SHGC 0.30 → 'the window allows 30 % of the sun's heat into the interior' (2018/2021/2022 objective).
Exam trap. Lower SHGC = less cooling load; it is NOT '70 % reflected' (some is absorbed and re-emitted).
Solar heat gain through glass
= SHGC × Incident solar radiation
Symbols · units
Symbols
W/m²
Answer unit
W/m²
Book topic
Building envelope
Where each value sits: W/m² → incident solar radiation, gain W/m²
Exam trap. Per m² of glass; multiply by the glass area for total watts.
Heat flow through a wall or window
Q = U × A × ΔT
Symbols · units
Symbols
U = U-factor (W/m² °C), A = area (m²), ΔT (°C)
Answer unit
W
Book topic
U-factor
Where each value sits: U → fenestration area, WWR, VLT, SHGC, U · A → fenestration area, WWR, VLT, SHGC, U · ΔT → fenestration area, WWR, VLT, SHGC, U
What it means
The U-factor is the heat that passes through 1 m² for each degree of temperature difference; lower U = better insulation. ECBC max for vertical fenestration ≈ 3.3 W/m²·°C (most zones).
Worked example. U 3.3, 20 m², ΔT 10 °C → 660 W.
Exam trap. U-factor in W/m²·°C; R-value is its inverse.
Reflectance and absorptance (opaque surface)
Reflectance + Absorptance = 1
Symbols · units
Symbols
—
Answer unit
no unit
Book topic
Cool roofs
Where each value sits: reflectance → reflectance + absorptance = 1, emissivity e · absorptance → reflectance + absorptance = 1, emissivity e
What it means
Whatever sunlight a roof does not reflect, it absorbs; a cool roof has high reflectance (≥ 0.7) AND high emittance (≥ 0.75) so it also radiates the heat away at night.
Worked example. Reflectance 0.7 → absorptance 0.3.
Exam trap. A cool roof REFLECTS heat (book EOC Q5).
Emissivity (thermal emittance)
e = Energy radiated by the material ÷ Energy radiated by a black body at same temperature
Symbols · units
Symbols
—
Answer unit
no unit (black body = 1)
Book topic
Cool roofs
Where each value sits: e → reflectance + absorptance = 1, emissivity e · black body → incident solar radiation, gain W/m²
What it means
How well a surface radiates heat compared with a perfect black body (e = 1); cool roofs need high emittance.
Worked example. e 0.9 radiates 90 % of the black-body rate.
Exam trap. Dimensionless, 0–1.
Interior lighting power allowance (building area method)
= Gross lighted floor area × Allowed LPD
Symbols · units
Symbols
m² × W/m²
Answer unit
W
Book topic
ECBC lighting
Where each value sits: floor area → annual kWh, built-up area m² → EPI · allowed LPD → lighting W, LPD W/m², floor area · W → lighting W, LPD W/m², floor area
What it means
ECBC cap on total lighting watts for a building type = floor area × allowed LPD.
Worked example. Hotel 4 × 1,000 m² at 10.8 W/m² → 43,200 W (book; 2011/2015/2021/2023/2024 objective).
Exam trap. Use the whole lighted floor area (all floors).
Lighting power density
LPD = Lighting power (W) ÷ Area (m²)
Symbols · units
Symbols
W, m²
Answer unit
W/m²
Book topic
ECBC lighting
Where each value sits: lighting W → lighting W, LPD W/m², floor area · floor area m² → annual kWh, built-up area m² → EPI · LPD → lighting W, LPD W/m², floor area
What it means
Watts per square metre — compare the actual installed lighting with the ECBC allowance.
Worked example. 8.11 kW ÷ 3,592 m² = 2.25 W/m² (2025 L-5).
Exam trap. kW × 1000 before dividing.
UPS efficiency
η = Output power ÷ Input power × 100
Symbols · units
Symbols
kW
Answer unit
%
Book topic
UPS
Where each value sits: output kW → UPS in / out kW · input kW → UPS in / out kW · heat loss → lighting W, LPD W/m², floor area
What it means
Output ÷ input; losses become heat that the AC must then remove — double penalty.
Worked example. 100 kW in, 90 kW out → 90 %; 10 kW of heat to the room.
Exam trap. In a UPS the inverter converts DC → AC (book EOC Q10).
Building envelope terms
Definitions the exam asks
ECBC
Energy Conservation Building Code (2007) for commercial buildings ≥ 100 kW / 120 kVA: envelope, HVAC, lighting, service hot water, electrical power; five climate zones — hot-dry, warm-humid, composite, moderate, cold (NOT 'cold-humid').
Compliance routes
Prescriptive (meet each limit), envelope trade-off (EPF — envelope performance factor), whole-building performance (simulation of the entire building).
Fenestration
Windows, skylights (slope < 60° from horizontal), glass doors, ventilators — not valves.
Star rating of buildings
BEE rates offices, BPOs, hotels, hospitals by EPI bands per climate zone; lower EPI → more stars.
BEMS / BMS
Building management system: central control of HVAC, lighting, pumps, with monitoring and scheduling.